Revision 2016/03, 6ELE, V1.14
4-87
When min. output frequency
≦
PID frequency
≦
lower bound of frequency and sleep function is enabled
(output frequency
≤
sleep frequency and time > detection time), frequency will be 0 (in sleep mode). If sleep
function is disabled, frequency command = lower bound frequency.
When PID frequency < min. output frequency and sleep function is enabled (output frequency
≤
sleep
frequency and time > detection time), output frequency =0 (in sleep mode).
If output frequency
≤
sleep frequency but time < detection time, frequency command = lower frequency. If
sleep function is disabled, output frequency =0.
10.17
PID Offset
Factory Setting: 0.00
Settings:
0.00~ 60.00Hz
The minimum output frequency in the PID control mode.
10.18
Feedback of PID physical quantity value
Unit: 0.1
Settings
1.0 to 99.9
Factory Setting: 99.9
When Pr.00.04 is set to 8, it will display 00:00 as follows.
This parameter is used only for display and has no relation with Pr.00.13, Pr.00.14, Pr.02.18 and Pr.02.19.
( the max. va lu e yo u wo ul d
l ike to co nve rt)
S etp oi nt
Fe ed ba ck val ue
10.19
PID Calculation Mode Selection
Factory Setting: 0
Settings
0
Series mode
1
Parallel mode
Series mode
P
10.02
I
10.03
D
10.04
10.05
10.10
10.07
10.06
10.01
+
-
+
+
+
Setpoint
Input Freq.
Gain
PID
feedback
Integral
gain
limit
Output
Freq.
Limit
Digital
filter
Freq.
Command
Parallel mode
P
10.02
I
10.03
D
10.04
10.05
10.10
10.07
10.06
10.01
+
-
+
+
+
Setpoint
In pu t Fre q.
G ai n
P ID
fe ed ba ck
In teg ra l
g ai n
l imi t
O utp ut
Fr eq .
L imi t
Di gi tal
fi lte r
Fr eq .
Co mman d