3-5 Technical Specification
Capacity
80KVA/64KW
120KVA/96KW
Rating Voltage
V
220/380, 230/400, 240/415
(3
ӥʳ
4W+Earth)
Voltage Regulation
%
-25 ~ +20
Input Current Harmonic Distortion
(Full Load)
% <
5
PFC (Full Load)
> 0.99
Frequency
Hz
50 / 60
Input
Frequency Tolerance
Hz
45 ~ 65
Output Voltage
V
220/380, 230/400, 240/415 (3
ӥʳ
4W+Earth)
Output Frequency
Hz
50 / 60
Total Harmonic (Linear Load)
%
Љ
3
Voltage
Regulation
Static
%
̈́
1
Dynamic
%
̈́
7 (10% ~ 90% Linear Load)
Frequency
Regulation
Interior Oscillator
Hz
̈́
0.05
Synchronized
%
̈́
5
Output
Overload
Љ
125%: 10minutes ;
Љ
150%: 1minute
Battery Backup
Intermittent
Audible
Warning
UPS Abnormal
Continuous
LED
UPS status: Normal, Bypass, Backup and Fault
Display
LCD
Input/Output, Bypass, Inverter, Frequency, Loading and Battery voltage, current,
UPS abnormal message and intelligent self diagnosis
Monitor
Monitor up to 31 PCs, Graphically display records and historical data and Fault records
retrieved
Remote
Control
Remote control the Inverter and alarm, setup password and auto-dial warning
Standard
RS232, Dry Contact Output
Interface
Optional
SNMP card, Modbus card, Relay I/O control card, Environmental sensor box, SNMP+5
Ports Hub
Parallel Redundancy
Yes (1+1 for two UPSs of the same capacity only!)
EPO
Standard (Local and Remote)
SRAM Event Log
Yes (500 records)
Parameter Configuration
Yes
Hot Standby Installation
Feasible
Battery Temperature Compensation
Optional
Others
Battery Start
Standard
Normal
%
94
Efficiency
ECO
%
97
Transfer Time
ms
0
Temperature
°
C
0
Д
40
Humidity (Non Condensed)
%
90
Noise (One Meter)
dBA
70
Dimension
Width
mm
520
520
Depth
mm
910
975
Height
mm
1165
1695
Overall
Weight
Kg
259
379