Part no.:
Delta model no.: HEC2000XA
Page 16
When the outer fan is running, Fan (Out) LED is solid green.
C
:
Touchpad Control:
1. ↑ ( UP button )
:
UP or increase
2. ↓ ( DOWN button )
:
DOWN or decrease
3. SET ( SET button )
:
Parametric setup
4. ON/OFF ESC ( ESC button )
:
Back or Power on/off( Pressing it about 5
seconds. )
2-2 Protection
Over Current Protection:
DC power board: 40 A
Over Temperature Protection:
DC power board: 89
±
4
o
C
Under Voltage Protection:
DC power board: 42
±
1.0 VDC
Over Voltage Protection:
DC power board: 59
±
1.0 VDC
Reverse Polarity:
Allow reverse voltage: 42 ~ 60 VDC
Short Ckt:
If compressor UVW short for any both phase the compressor will not operate.
Compressor H/T Protection:
Tcomp
≧
105
o
C
Eva L/T Protection:
TEVA < 0
o
C
3. Environmental Condition
Operating Temperature
-40 °C ~ +55 °C (-40 °F ~ +131 °F)