- 2 -
Electrical Specifications
Model
Item
16ES200
24ES200
32ES200
40ES200
60ES200
20EX200
Power supply
voltage
100 ~ 240VAC (-15% ~ 10%)
,
50/60Hz
r
5%
Connector
European standard removable terminal block (Pin pitch: 5mm)
Operation
DVP-ES2 starts to run when the power rises to 95 ~ 100VAC and stops
when the power drops to 70VAC. If the power is suddenly cut off, the MPU
will continue running for 10ms.
Power supply
fuse
2A/250VAC
Power
consumption
30VA 30VA 30VA 30VA 30VA 30VA
DC24V current
output
500mA 500mA 500mA 500mA 500mA 500mA
Power supply
protection
DC24V output short circuit protection
Voltage
withstand
1,500VAC (Primary-secondary)
,
1,500VAC (Primary-PE)
,
500VAC (Secondary-PE)
Insulation
resistance
> 5M
ȍ
at 500VDC (between all I/O points and ground)
Noise immunity
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 1KV
RS: 26MHz ~ 1GHz, 10V/m
Grounding
The diameter of grounding wire shall not be less than that of L, N terminal of
the power supply. (When many PLCs are in use at the same time, please
make sure every PLC is properly grounded.)
Environment
Operation: 0°C~55°C (temperature), 50~95% (humidity), pollution degree 2
Storage: -25°C~70°C (temperature), 5~95% (humidity)
Vibration/shock
resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 &
IEC 68-2-27 (TEST Ea)
Weight
R: 377g
T: 351g
R: 414g
T: 387g
R: 489g
T: 432g
R: 554g
T: 498g
R: 696g
T: 614g
R: 462g
T: 442g
Input Point
Input point type
Digital input
Input type
DC (SINK or SOURCE)
Input current
24VDC, 5mA
Input No.
X0, X2
X1, X3 ~ X7
X10 ~ X17, X20 ~
#1
Off
ĺ
On
>15VDC
Action level
On
ĺ
Off
< 5VDC
Off
ĺ
On
2.5
ȝ
s 20
ȝ
s 10ms
Response time
On
ĺ
Off
5
ȝ
s 50
ȝ
s 10ms
Filter time
X0 ~ X7
Adjustable within 0 ~ 20ms in D1020 (Default: 10ms)
Input impedance
4.7K
ȍ
Output Point
Output point type
Relay-R
Transistor-T
Output point number
All
Y0, Y2
Y1, Y3 Y4~Y17, Y20~
#1
Voltage specification
< 250VAC, 30VDC
5 ~ 30VDC
#2
Maximum load
Resistive
2A/1 point (5A/COM)
0.5A/1 point (4A/COM)