background image

32

33

EN

SW1

Configuring the 

 

technical unit

OFF

Master

ON

Extension (refer to the 'Extension option' §)

SW2

Production mode

OFF

Heat (boiler or non reversible heat pump)

ON

Heat/Cool (reversible heat pump)

SW3

Valve actuator type

OFF

Thermal 2 positions (number of outputs 8 max.)

ON

Motorised 3 positions (number of outputs 4max.)

SW4

Valve control direction

OFF

Normally closed

ON

Normally open

SW5

Override mode 

(e.g: initial heating)

OFF

No

ON

Yes (valves and circulator active)

SW6

Heat pump change-over  
communication 
direction

OFF

Heat pump to Technical Unit (Change-over input). The 
heat pump delivers its production mode to the TU.

ON

TU to heat pump (change-over output). The TU delivers 
its production mode to the heat pump.

SW7

Heat pump change-over  

configuration

OFF

Contact closed= Heat mode 
Contact open = Cool mode

ON

Contact closed= Cool mode 
Contact open = Heat mode

SW8

Type of 'water 
monitoring' 
measurement.

OFF

Absence of dew point measurement or sensor with 
a Delta Dore condensation sensor (For cooling only, 
shuts the system down if condensation is detected).

ON

Initial Cool or Heat temperature with CTN 10KW 
sensor at 25°C (shuts the system down if the water is 
too hot or too cool).

1

ON

6

5

4

3

2

DIP

88

7

SW5: Override mode

This mode overrides the 100% operation for initial heating. Set switch 5 to ON.
On the technical unit, the circulator LED and valve output LEDs are illuminat d. The 'Status' 
LED is off. 
On the room thermostat (RT) or the programmable thermostat (PRT) a 

specific display indicates that initial heating is in progress.

All the switches are set to OFF by default.

HP: Heat pump 

 TU: Technical unit

5/  SWITCH CONFIGURATION

6/  ASSOCIATING A ROOM THERMOSTAT WITH 
A TECHNICAL UNIT

Example: 

Associated outputs (CF20)

Controlled outputs

Thermostat 1

1

Y1, Y2, Y3

Thermostat 2

4

Y4, Y5

Thermostat 3

6

Y6, Y7, Y8

Y1 N

N

N

N

N

N

N

N

Y2

Y3

Y4

Y5

Y6

Y7

Y8

5 6

7

8

9 10 11 12 13 14 15 16 17 18 19 20

Th 1

Th 2

Th 3

6.1  WITH A ROOM THERMOSTAT (RT)

 Press and hold the 1st and 4th button for 3 seconds,  

then release. 
 

 The screen displays 

CF20

. Press OK to open the setting, 

then press + and - to select the output with which the 
thermostat will be associated.  

Confirm with OK.

 

 

 The screen displays 

CF21

Select the transmitter and press OK. 
 

 The screen displays 

CF05

Select the thermostat type and press OK.

3 s

1

2

(1)

Output number

1 to 16 depending on the system.

Transmitter type

0

Underfloor heating

1

Heater

2

Ceiling or ductable

(2)

Thermostat type

0

Zone thermostat

1

Master Thermostat

(2)

 CF05: the Master thermostat enables the centralised use of ON/OFF and HEAT/COOL 

 

(at least one Master thermostat is required in an installation without a programmer).

Summary of Contents for DELTA 8000 BT

Page 1: ...EN Technical unit for Delta 8000 system DELTA 8000 BT Installation instructions ...

Page 2: ... Associating a room thermostat with a technical unit 33 6 1 With a Room Thermostat RT 33 6 2 With a Programmable Room Thermostat PRT 34 7 Configuring the technical unit 35 7 1 With a room thermostat RT 35 7 2 With a programmable room thermostat PRT or programmer PROG 36 8 Restoring the technical unit to factory settings 37 8 1 With a room thermostat RT 37 8 2 With a programmable room thermostat PR...

Page 3: ... Red circulator and burner LEDs P and G Red valve LEDs 1 to 8 On Normal operation Relay closed Output on On Off Initial heating of the slab Relay open Output off Off Slow flashing Association mode Quick flashing Defect in progress Defect in progress 1 ON 6 5 4 3 2 DIP 8 8 7 Configuration switches Status LED Water monitoring input Circulator LED Burner LED Change over input output Valve outputs Valve...

Page 4: ...tputs dry contact 2A Max 230V Valve outputs If you use 3 position actuators you will only be able to connect 4 valves to the technical unit switch SW3 ON If you need more outputs use another technical unit in Extension mode Valve power supply 24VAC DC or 230 V 240 V Main power supply 230 V 240 V Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y8 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Y1 SW3 OFF SW3 ON N N N N N N N N N ...

Page 5: ...at manual PRT zone 1 PRT zone 2 PRT zone N BT Master SW1 OFF BT Extension SW1 ON 1 8 sorties 1 ON 6 5 4 3 2 DIP 8 8 7 1 ON 6 5 4 3 2 DIP 8 8 7 Bus 30m max Bus 30m max 1 8 sorties max 1 8 sorties max 1 8 sorties max BUS 1 BUS 2 BUS Bus 30m max BUS 1 BUS 2 BUS Example 3 Regulation with room by room programming PRT Programmable Room Thermostat Programmer RT zone 1 RT zone 2 RT zone N Bus 30m max BUS ...

Page 6: ...lation Wireless programmers centralised programming Wireless programmable thermostats regulation room by room programming Window magnetic contacts activates the Frost Protection mode when a window is opened Presence absence detectors lower the temperature setting when the premises are left empty for a long period of time Outdoor temperature sensor Bus 1 8 sorties max Wireless programmer Radio bus ...

Page 7: ...ride mode This mode overrides the 100 operation for initial heating Set switch 5 to ON On the technical unit the circulator LED and valve output LEDs are illuminat d The Status LED is off On the room thermostat RT or the programmable thermostat PRT a specific display indicates that initial heating is in progress All the switches are set to OFF by default HP Heat pump TU Technical unit 5 SWITCH CON...

Page 8: ...t with which the thermostat is to be associated Confirm with OK The screen displays CF21 Select the transmitter and press OK The screen displays CF22 Select the limitation value and press OK to confirm To exit the current mode press or turn the dial 3 s 1 CF20 a product associated with an output also controls the following outputs in the same manner if these are not associated 7 CONFIGURING THE TE...

Page 9: ...orm the setting Confirm with OK 1 CL04 only appears in Heat production mode SW2 OFF refer to the technical unit s manual and for underfloor heating CF21 0 or for ceiling ductable CF21 2 Passive cooling water flow for cooling heating in OFF mode 2 CL06 CL07 if the limit is exceeded or reaches switch over to OFF mode The defect comes up on the thermostat screen see Troubleshooting Water monitoring i...

Page 10: ...the connection of a safety device to the system bimetallic strip on the circulator or condensation sensor aimed to monitor the system s water temperature and to cut off the water flow if necessary Principle for the detection of excessively hot or cold water Depending on the entered temperature limit value to be set at the time of installation the system scans the water temperature and reconciles i...

Page 11: ...d by disturbances Move your products around to check the radio range Radio reception defect on an associated presence detector Battery of an associated window magnetic contact defective Replace the batteries of the prod uct in question Battery of an associated presence detector defective 10 TROUBLESHOOTING Main power supply 230V 240V 10 50 60 Hz Valve power supply 24V or 230V 240V 4A Max for all v...

Page 12: ...www deltadore com 09 18 ...

Reviews: