Delta Controls
Document Edition 4.1
Page 7 of 41
N
OTE
: AI2 (and AI3 for the DNT-T221) are not configured through the Configuration
Menu. These objects must be configured through the OWS (i.e., for Scale/Units) – except
when AI2 is used for VAV airflow. Refer to
on page 33
for more
information.
SERVICE TOOL MODE (KEYPAD)
A new
BACstat II Quick Reference Card
for Service Tool Mode (product number REF-817) is
available for quick and easy reference, and for navigation of the Service Tool features. One is
shipped with the product, and additional copies can be ordered as necessary.
1.
S
ERVICE
T
OOL
M
ODE
U
SER
A
CCESS
&
N
AVIGATION
Access to Service Tool Mode and its associated menu options is
not
protected by an access code or PIN.
However, user access must be enabled (via AV32 or the setting located in the Configuration Menu) and
the valid key sequence must be entered.
•
To enter Service Tool mode, first press the Down Arrow (
▼) and then the Up Arrow (▲), and hold
them both down for at least 5 seconds (which is the opposite sequence to the Configuration menu).
There is no PIN or password.
•
Once you have entered the valid user key sequence you will gain access to Service Tool Mode, and
SEr
will be displayed immediately along with a main menu of several options.
•
You may now use the up and down arrow buttons to navigate through the main menu options, and
the N
EXT
or P
REVIOUS
buttons to navigate the submenus and their associated options.
•
Once you have navigated to the desired item you wish to display or change, use the arrow buttons to
make any necessary changes. Once the changes are made or you wish to move on, press N
EXT
or
P
REVIOUS
.
•
If at any time you do not press a button for 30 minutes, the BACstat will exit Service Tool Mode
and return to normal display mode. Any outputs commanded manually will remain in manual, and a
VAV box commanded to various Air Balancer modes (Minimum, Maximum, Close, Open, Zero
Calibration) will also remain as commanded. A subsequent user command (
CtL
) is required to put
the BACstat and associated outputs back under control (or Auto).
2.
S
ERVICE
T
OOL
M
ENU
O
PTIONS
Service Tool Mode contains two menus: the Main menu and an Air Balancer menu (which is only
available when the application is configured for VAV).
Air Balancer Menu Options
Menu
Item
Description
Displayed on line 2 of the LCD (center screen) to indicate you are at the Main menu of the
Service Tool Mode.
[
Option
]
Service Tool Mode has these following main menu options, which you rotate through using
the arrow keys. Press the N
EXT
or P
REVIOUS
buttons to select the option and navigate the
submenus.
•
•
To calibrate Inputs AI1 to AI3 as compared to an external measuring device.
Navigate past the inputs you don’t wish or need to calibrate.
To manually command AV1 to AV3 (0-100% for tri-state or PWM, and O
FF
or
O
N
for binary outputs), associated with OP1 to OP3 respectively. This allows
for end-to-end commissioning of output devices. Navigate past the outputs you