![Delta Controls DNT-T103 Application Manual Download Page 38](http://html1.mh-extra.com/html/delta-controls/dnt-t103/dnt-t103_application-manual_2475113038.webp)
DNT-T103 & DNT-T221 Application Guide
Page 38 of 41
Document Edition 4.1
With V3.21 Firmware
: When connected to LINKnet, local display and button handling should be
disabled (i.e., AVx15 = 1111), which is the default when you set the LINKnet Communications
Setting to On. This way, the LCD and buttons are fully accessible from the Application Controller for
custom programming. Then, with GCL+ and the LCD and AI objects resident up in the Application
Controller, you program the BACstat to operate as you want (similar to how ISTATs were
programmed) – all BACstat functionality is written in GCL+ located in the Application Controller.
Note that none of the AV objects are accessible with V3.21 firmware.
With V3.22 Firmware or Higher
LCD Object Property Values (for GCL+ Programming)
: You may disable local display and button handling (i.e., AVx15 =
1111) and program everything in GCL+ in the Application Controller as previously described for
V3.21 firmware. Or, by setting the Display Code to something other than 1111, the display and
buttons may be configured to function locally and GCL+ commands from the Application Controller
for display and button handling (via the LCD object) are ignored. This may be the preferred method
as no GCL+ needs to be written to handle setpoint adjust and the display of values on the LCD.
The following is a table of LCD object properties and associated values that can be used in GCL+
programming in a DAC/DSC product for BACstats when connected on its LINKnet network.
(Display code set to = 1111)
LCD Property Name
Values & Description
Line1
Notes
For sending a value to Line 1
Line2
For sending a value to Line 2
Line3
For sending a value to Line 3
Line1Units
0
= º icon is turned off
1
= º icon is turned on
Only available with V3.30
DAC/DSC firmware.
Line2Units
0
= º icon is turned off
1
= º icon is turned on
Only available with V3.30
DAC/DSC firmware.
Line3Units
0
= No Unit icons
1
= º icon only
2
= ºC
3
= ºF
4
= %
5
= AM
6
= PM
Only available with V3.30
DAC/DSC firmware.
Blink
0
= Blinking is disabled
1
= Entire LCD display blinks
Occupancy
0
= No House/Man (Disabled)
1
= House only (Unoccupancy)
2
= House & Man (Occupancy)
The values shown are for V3.30
DAC/DSC firmware. For V3.22
firmware, the values of 1 and 2
are reversed.
Sun
0
= Sun icon is turned off
1
= Sun icon is turned on
Applicable only for V3.22
DAC/DSC firmware.
Moon
0
= Moon icon is turned off
1
= Moon icon is turned on
Applicable only for V3.22
DAC/DSC firmware.
SunMoon
0
= No Sun or Moon (Disabled)
1
= Moon only
2
= Sun only
Applicable only for V3.30
DAC/DSC firmware.
Fan
0
= No Fan icons - All turned off
1
= Fan icon only
2
= Fan with Air Flow Wave 1