Delta Controls ADM-2W704 Installation And Application Manual Download Page 8

Access Door Module ADM-2W704 (Rev 1.3) Installation & Application Guide 

 

 

Page 8 of 26 

 

Access Door Module

 

P

OWER 

W

IRING

 

 
All power wiring must be completed by a licensed electrician and conform to the National Electrical Code, 
ANSI/NFPA 70, and local codes and regulations. 
 
The Access Door Module must be powered by the UL listed, 24VAC, 50/60 Hz Basic Electric transformer, 
Model 7511CBDH, or equivalent. Connect low voltage power (24VAC) from the UL listed transformer to the 
AC power terminals, marked as 24~. 
 

 

 

The Access Door Module needs to use its own dedicated transformer as its 24 VAC 
power source.  You may not connect several controllers to the same transformer.

 

 

Use 14 AWG minimum for wiring the AC in (i.e.120VAC) side of the UL listed 
transformer, per NEC requirements. 

 

Keep adequate spacings between battery, power limited field wiring and AC in. 
Suggest using UL recognized cable ties. Minimum .25” separation must be provided. 

 

Use proper strain relief for any flexible wiring. 

 

Use bushings on rough surfaces to protect cabling from abrasion. 

 

Do not wire power cord behind electrical enclosure. 

 

 

 

 

 

All terminals are acceptable for Class 2 Circuit connections only 

 

Use copper conductors only 

 

Apply minimum 6.0 lb-in torque for tightening field wires into the terminal blocks 

 

B

ATTERY 

B

ACKUP 

W

IRING 

(N

OT TO BE CONNECTED IN 

UL

 APPLICATIONS

 
The Access Door Module has been designed with a battery circuit to provide the option of both battery 
charging and battery backup for the controller.  The battery backup supplies power to the controller, its 
output devices (if power from the board), and Auxiliary power connections.  Battery backup should be used 
when using Magnetic Locks on any doors that you would like to keep locked when there is a power failure or 
having the Access Control System be functional in the event of a power loss. 
 
The battery charging circuit has been designed for the following battery specifications: 

 

7 Amp Hours   

 

Sealed Lead Acid battery only 

 

Capable of both a trickle charge and bulk charge 

 

Use supplied 0.25” Faston Lugs for connecting battery 

 
Using a 7 AH Battery, the table below shows approximately how long the battery will last when fully 
charged. (Not evaluated by UL)  
 

Lock Duty (Battery Full Charge) 

Battery Back-up Time (hours) 

No lock activity, with Access System Manager backed-up 

50% duty lock activity, with Access System Manager backed-up 

100% duty lock activity, with Access System Manager backed-up 

No lock activity 

12 

50% duty lock activity 

100% duty lock activity 

Note: Battery back-up times are approximations based on loads specified with a new battery. Old 

batteries will not perform as well due to normal battery degradation.

 

 

Summary of Contents for ADM-2W704

Page 1: ...etworked together to a maximum of 12 Access Door Modules to provide access control of up to 24 doors TABLE OF CONTENTS PRODUCT DESCRIPTION 1 TABLE OF CONTENTS 1 MODEL NUMBERS 2 UL AUTHORIZED ACCESSORI...

Page 2: ...ad Range Single Gang Box Mount Sentinel Prox SR 2400 4 to 5 5 inch Read Range Metal Compensated Indoor Outdoor Sentinel Prox MM 6800 6 to 8 inch Read Range Metal Compensated Indoor Outdoor Sentinel Pr...

Page 3: ...battery charging and battery back up of the controller as well as all devices connected and powered from the controller DC Power out 14 VDC 0 25A with a resetable fuse can supply one Access System Man...

Page 4: ...tatus o 1 Battery Status o 2 Door 5 VDC Power Status o 2 Door 12 VDC Power Status Outputs 2 Door Locks Form C Relay rated 24VDC AC 5A with MOV protection internally supplied with 12 VDC as above 2 Aux...

Page 5: ...oys Wiegand 26 communication protocol and was verified in the evaluation UL has not evaluated the following features of the ADM 2W704 and therefore should not to be connected in UL applications Batter...

Page 6: ...Access Door Module ADM 2W704 Rev 1 3 Installation Application Guide Page 6 of 26 Access Door Module BOARD LAYOUT ACCESS DOOR MODULE All Terminal Class 2...

Page 7: ...he associated output CONTROLLER ADDRESS DIP SWITCHES Each individual DIP switch represents a pre defined value as printed on PCB beside the address block which added together forms the device address...

Page 8: ...ield wires into the terminal blocks BATTERY BACKUP WIRING NOT TO BE CONNECTED IN UL APPLICATIONS The Access Door Module has been designed with a battery circuit to provide the option of both battery c...

Page 9: ...Delta Controls Access Door Module Page 9 of 26 24 VAC Access Door Module Power Connection Wiring Detail Battery Connection Wiring Detail Not evaluated by UL...

Page 10: ...ss Door Module ADM 2W704 Rev 1 3 Installation Application Guide Page 10 of 26 Access Door Module DC Power Out Used Power and Battery Backup Access System Manager Auxiliary Power Wiring Not Evaluated b...

Page 11: ...duct is shipped configured as a Fail Secure door See diagram below The tamper switch input is connected to a standard single contact switch such as the Locknetics Security Model 7766 either the N O or...

Page 12: ...oor Module 12 VDC is a linear power supply which is required by most proximity card reader manufacturers You should follow the wiring and wire type specifications of the card reader manufacturer that...

Page 13: ...Delta Controls Access Door Module Page 13 of 26 AWID HID Prox Card Reader Wiring...

Page 14: ...ieve the status and to interrupt the Door Lock for egress The table and diagram below show how the Request to Exit should be configured and wired for the Door Lock type chosen When using a Type 3 or T...

Page 15: ...t configure the circuit If the Door Lock is configured as fail safe a jumper needs to be put in place of the RTE Contact The diagram below shows how the RTE circuit is configured when not using an RTE...

Page 16: ...rams below Each EOL circuit is based on 10K Ohm 5 resistors EOL resistors should be installed at the end of the line at the device not at the Access Door Module controller Placing an EOL at the Access...

Page 17: ...onitor supervise a Normally Open contact to indicate Trouble when there is an Open Circuit wires cut A short circuit contact bypassed will not indicate Trouble but will generate an Alarm condition Con...

Page 18: ...y Open contacts When using a Type 3 or Type 4 EOL Circuit and a Request to Exit button that has a single pole switch make sure that the 10K Ohm resistor is on the input leg of the circuit not the grou...

Page 19: ...the Type 3 or Type 4 EOL Circuit and a Request to Exit button that has a single pole switch make sure that the 10K Ohm resistor is on the input leg of the circuit not the ground side of the circuit o...

Page 20: ...elay Output SPDT Not to be connected in UL applications BO7 B LED1 BO8 B LED2 BO9 N A Trouble LED Door Lock Wiring Detail The Door Lock output is wired straight back to the Access Door Module as shown...

Page 21: ...h door is an SPDT relay and can be wired as N O and or N C It is controlled from a single software output The contacts are rated at 24VAC DC 5A Wiring Detail for switching a large load 120VAC Motor is...

Page 22: ...ty of propagation of 66 or higher Topology Ensure the cable is installed as a daisy chain from one device to the next Max Controllers Access Door Modules The maximum number of controllers per LINKnet...

Page 23: ...OLOGY CONFIGURATION NOT EVALUATED BY UL With V3 22 firmware the Access Door Module is a LINKnet device that acts as extended I O to the master controller the Access System Manager Up to 12 Access Door...

Page 24: ...al Reference Manual for further details on configuring the LINKnet network or changing baud rates etc See RS 485 Network Installation Guide DOC818 11 for details on wiring and terminating the LINKnet...

Page 25: ...uations Pst 1 Plt 0 65 EN 61000 6 1 2007 Generic Immunity Standard Part 1 Light Industrial Residential EN 55024 2010 Immunity Requirements for Information Technology Equipment EN 61000 4 2 ESD Immunit...

Page 26: ...ipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause ha...

Reviews: