![DeLonghi CLIMAVENETA HED HCAT 0011 SE Installation And Service Manual Download Page 42](http://html1.mh-extra.com/html/delonghi-0/climaveneta-hed-hcat-0011-se/climaveneta-hed-hcat-0011-se_installation-and-service-manual_2469227042.webp)
40
HED-HCAT SE FREE COOLING
ENGLISH
The mask Gb, which only activates in the plan mode, is used to define:
a) number of units set in the stand-by mode
Factory value: 0
Range: 0÷1
b) automatic rotation interval of units in pLAN network
Factory value: 24
Range: 1÷240
“Set the configurations according to the enclosed display page”
Unit rotation
unit in stand-by:
1
Rotation time:
024h
The mask Gc, which only activates in the plan mode, is used to define:
a) enabling of support in cooling/heating of unit in pLAN network
Factory value:YES
Range:YES-NO
b) forcing delays for low and high ambient temperature
Factory value: 003/003
Range: 000÷999
“Set the configurations according to the enclosed display page”
Unit forced
for temperature;
YES
Low temp. delay
003
High temp. delay
003
The mask Gd, which only activates in the plan mode, is used to define:
a) the low ambient temperature differential for forcing network units:
Factory value: 8.0°C
Range: 0.0÷99.9°C
b) the low ambient temperature offset for forcing network units:
Factory value: 4.0°C
Range: 0.0÷99.9°C
“Set the configurations according to the enclosed display page”
Unit forced
for low temperature
Difference:
008.0°C
Offset:
04.0°C
The mask Gd, which only activates in the plan mode, is used to define:
a) the high ambient temperature differential for forcing network units:
Factory value: 8.0°C
Range: 0.0÷99.9°C
b) the high ambient temperature offset for forcing network units:
Factory value: 4.0°C
Range: 0.0÷99.9°C
“Set the configurations according to the enclosed display page”
Unit forced
for high temperature
Difference:
008.0°C
Offset:
04.0°C
Click on the ESC key to return to the MANUFACTURER
menu.
To enter the PARAMETERS menu, position on PARAME-
TERS with the scrolling selectors and click on the enter
key.
CONFIGURATION
Parameters
Carel EXV Driver
Delay times
Initialization
Gb
Gc
Gd
Ge