37
HED-HCAT SE FREE COOLING
ENGLISH
The display page T7 is used to set the freecooling off time due to high humidity limit
Range 0÷ 999
Unit of measurement seconds
Time off freec.
T7
For humid.
limit
_ _ _ min
the display page T10 is used to set:
Range 0 ÷ 9999
Unit of measurement seconds
Delay alarm
T10
Freecooling
_ _ _ _ sec
Switch off the unit to confirm the set default values.
Set default
values
Switch off unit
to confirm
The display page V0 is used to reinstall default parameters..
Range 0 ÷ 9999
Insert Password
V0
To install default param.
value
0000
The display page V0 is used to set the password .
Range 0 ÷ 9999
New manufacturer
V2
password
0000
The display page V1 can be used to delete the alarm records
Range No ÷ Yes
Story reset
V1
alarm
Yes / No
Click on the Esc key to return to the Manufacturer menu.
To enter the Initialization menu, use the scrolling selectors
to position on Initialization and click on the enter key.
Configuration
Parameters
Carel EXV Driver
Delay times
Initialization