Figure 20. I/O module installation
1
Ejector lever
2
Orange release tab
3
I/O module
Important points
The S6100–ON is designed to support two hot-swappable power supplies with integrated fans that provide cooling for the chassis.
•
The S6100–ON ships with two power supplies.
•
The PSU slides into the slot smoothly. Do not force the PSU into a slot as this action may damage the PSU or the S6100-ON chassis.
•
The S6100–ON supports AC and DC power supplies with two air-flow directions—I/O to PSU and PSU to I/O. The S6100–ON does
not support mixing PSU types. The fan airflow direction for the PSUs must be the same.
•
Module power is software controlled. You do not see module LEDs when the system powers up.
CAUTION:
DO NOT mix airflow directions. Both power supplies must use the same airflow direction—I/O to PSU or PSU to
I/O.
WARNING:
Although the switch can run on one PSU, Dell highly recommends using two PSUs for full redundancy and extra
cooling. To avoid overheating when the switch is running with a single PSU, install the second PSU.
WARNING:
ESD damage can occur if components are mishandled. Always wear an ESD-preventive wrist or heel ground strap
when handling the S6100–ON and its components.
28
S6100–ON installation