background image

P

LANNING

l

Overview

l

Description

l

Platform information

l

LCN node slot requirements

l

Experion nodes slot requirement

l

Memory configuration for Dell R330XL

l

System specifications

l

Industrial regulatory compliance

l

Light industrial regulatory compliance

2.1

Overview

Platforms sold by Honeywell are engineered for the process control mission of Experion and TPS
systems to provide consistent and robust performance. Through an extensive qualification process,
Honeywell defines specific peripheral devices, slot locations, and BIOS settings for best performance
and reliability, sometimes even adding cooling fans for longer service. Honeywell platforms are then
built to Honeywell specifications by the computer manufacturer.

Honeywell engineering has tested theDell PowerEdge R330XL serverwith other Honeywell hardware
and software and has qualified its use for specific configuration items as identified in the Software
Change Notice (SCN). The server is not a standard Dell model and cannot be ordered independently
from Dell. The Technical Assistance Center (TAC) is well trained and supports Honeywell platforms.
Use of any other server including a similar Dell model, is considered a project special and its TAC
support is limited according to the services policy.

The Honeywell-based Dell PowerEdge R330XL server provides the functionality of a server-based PC
running the Microsoft Windows server operating systems.

The release of this server is based upon RAID-5 and dual power supply design to provide computer-
based functionality for certain Experion systems and the TPS systems.

The Dell PowerEdge R330XL servers are shipped with the Tab number 51156061-100 8GB base
memory model & its replaced by 51156061-200 (16GB base memory model).

l

Software requirement

l

BIOS configuration

2.1.1

Software requirement

The server runs on the following operating system.

l

Microsoft Windows Server 2008 R2 (64-bit) for EPKS R41x.x and R43x.x release.

l

Microsoft Windows Server 2016 for EPKS R50x.x release.

The server platform runs the latest version of the following Experion server.

- 9 -

CHAPTER

2

Summary of Contents for PowerEdge R330XL

Page 1: ...R330XL Honeywell Server Planning Installation and Service Guide HWDOC X452 en D August 2020 ...

Page 2: ...al Sàrl While this information is presented in good faith and believed to be accurate Honeywell disclaims the implied warranties of merchantability and fitness for a purpose and makes no express warranties except as may be stated in its written agreement with and for its customer In no event is Honeywell liable to anyone for any direct special or consequential damages The information and specifica...

Page 3: ... 1 FTE supervisory Default 14 2 5 2 Cnet configuration using PCIC interface 14 2 6 Memory configuration for Dell R330XL 14 2 6 1 8GB consisting of two 4GB ECC DDR4 UDIMM for Dell PowerEdge R330XL server servers 15 2 6 2 16GB consisting of two 4GB ECC DDR4 UDIMM for Dell PowerEdge R330XL server servers 15 2 6 3 16GB Consisting of two 8GB ECC DDR4 UDIMM for Dell PowerEdge R330XL server servers 15 2 ...

Page 4: ...ers in cabinet 30 3 5 Starting the server 32 3 5 1 Turning on the power 32 3 5 2 Configuring RAID in Dell R330XL server 32 Chapter 4 Operation 34 4 1 Server overview 34 4 1 1 Front view of Dell R330XL server 34 4 1 2 Rear view of Dell R330XL server 35 4 2 Network connections 35 4 2 1 Ethernet network 35 4 2 2 ControlNet Network 35 4 3 Configuring ControlNet interface card 36 4 3 1 Installing Contr...

Page 5: ...5 5 2 To enter the BIOS 43 5 5 3 BIOS settings for Tab 51156061 100 and 51156061 200 43 5 6 Spare parts 50 5 7 Troubleshooting 50 5 ...

Page 6: ...rface to LCN is not used The LCN MAU is disconnected and or the LCNP board is removed Redundant ELCN Bridges are required if the ELCN node is communicating with any other existing coaxial based LCN node Some LCN nodes may have been replaced by their ELCN equivalent nodes and overall system features architecture will differ from that of a non ELCN integrated system classic LCN TPN system In this ca...

Page 7: ...cribes configuration tasks needed for TPS Nodes Virtualization Planning and Implementation Guide EPDOC X147 en A Implementing networks Preparing ESXi host Administering virtualization Server and Client Planning Guide EPDOC X128 en 510A High level planning design for Experion servers clients controllers Process Operations Manual SW11 601 Process operations alarm message handling reporting history f...

Page 8: ...ssues special considerations Customer Release Guide R687 CRG 687 TPN TPS Migration information ELCN migration Information included TPN R687 Software Change Notice TNDOC X166 en 6871A Document changes compatibility and migration installation processes for the TPS Process Network Release of R687 software Experion Control Building User s Guide EPDOC XX19 en 510A Procedures for basic tasks in the Cont...

Page 9: ...CN The server is not a standard Dell model and cannot be ordered independently from Dell The Technical Assistance Center TAC is well trained and supports Honeywell platforms Use of any other server including a similar Dell model is considered a project special and its TAC support is limited according to the services policy The Honeywell based Dell PowerEdge R330XL server provides the functionality...

Page 10: ... 6 GHz 8M Cache 8 00GT s QPI Turbo HT 16Gb UDIMM 2x8GB 300GB 15K RPM Serial Attach SCSI 12Gbps 2 5in Hot plug Hard Drive QTY 4 PERC H730 RAID Controller 1GB Cache RAID 5 configuration MZ PCEH08 300GB 2 5 15K RPM SAS HDD to use as a Hot Spare not supplied with Standard configuration customer need to buy it if hot spare is required EP COAR28 Windows Server 2008 R2 COA EP COAS16 Microsoft Windows Ser...

Page 11: ...15K RPM Serial Attach SCSI 12 Gbps 2 5in Hot plug Hard Drive QTY 4 PERC H730 RAID Controller 1 GB Cache l 1 serial 1Video 2 USB V3 0 2 RJ45 1 ID push button with blue amber LED Rear Panel l 2 USB 2 0 ID push button with blue amber LED 1 video 1 system power on off button Front Panel l Broadcom 5720 1GBE Dual Port Ethernet NIC with failover and load balancing l Expansion slots 2 PCIe slots using ri...

Page 12: ...entation l Dell documentation 2 3 1 Honeywell documentation The following table lists the Honeywell publications that may be useful when installing or operating your system Publication Contains information about Fault Tolerant Ethernet Installation and Service Guide Installing and using FTE on a TPS or Experion PKS node 2 3 2 Dell documentation The following table lists the Dell publications that ...

Page 13: ...stems Hardware Owner s Manual Removing and replacing the parts Technical specifications Configuring the system Troubleshooting Product Documentation CD www dell com Rack Installation Instructions Sliding Rails Installing the server in a server rack or cabinet Packaged with the computer www dell com Windows Installation Instructions and Important Information Initialization the Windows operating sys...

Page 14: ...erface you must use Magma PCIe to PCI converter box Slot number Description Option Slot 1 PCI Slot Gen 3 Magma Host Card Slot 2 PCI Slot Gen 3 2 6 Memory configuration for Dell R330XL Standard memory for Dell PowerEdge R330XL server server is Tab 100 8GB 2x4GB UDIMM 2133MHz or faster and Tab 200 16GB 2x8GB UDIMM 2133MHz or faster and it must be installed in pairs The label on the outside of the sh...

Page 15: ...GB ECC DDR4 UDIMM for Dell PowerEdge R330XL server servers The following table provides memory configurations layout for 16GB consisting of two 4GB ECC DDR4 UDIMM for Dell PowerEdge R330XL server servers DIMM socket Memory size Channel A1 4GB UDIMM 0 A3 4GB UDIMM A2 4GB UDIMM 1 A4 4GB UDIMM In order to support EPKS R50x x release memory needs to be upgraded to 16GB if existing 4GB memory modules a...

Page 16: ...DIMM socket Memory size Channel A1 8GB UDIMM 0 A3 8GB UDIMM A2 8GB UDIMM 1 A4 8GB UDIMM Tab 51156063 100 For R51x x customer needs to discard existing 4GB memory modules and order 4 x8GB memory modules 2 7 System specifications Microprocessor Microprocessor Skylake Intel Xeon E3 1270 V5 3 6 GHz 8M Cache 8 00GT s QPI Turbo HT Intel Smart Cache 8 MB Chipset Intel C236 series PCIe slots 2 PCIe slots ...

Page 17: ...200 16GB 2x8GB Maximum RAM Tab 100 16 GB 4x4 GB UDIMM DDR4 2133 MHz or faster Tab 200 32GB 4x8GB Raid controller RAID controller PERC H730 RAID Controller 1 GB Cache F W Version 25 4 0 0017 or higher Optical disk drive DVD drive SATA DVD R W Video Video type Matrox G200e Controller Network interface Adapter type On Board LOM 1GBE Dual Port BCM5720 GbE LOM Power The following provides the specifica...

Page 18: ...Environmental 18 Chapter 2 Planning ...

Page 19: ...ude derating of 1 C per 300 m 1 8 F per 1 000 ft to 3048 m 10 000 ft is applicable Direct sunlight is not allowed Operating humidity 10 to 80 non condensing with a maximum humidity gradation of 10 per hour and 29 C 84 2 F maximum dew point Storage humidity 5 to 95 non condensing with a maximum humidity gradation of 10 per hour and with 33 C 91 F maximum dew point Note Atmosphere must be non conden...

Page 20: ...and Control Systems Temperature and Humidity ANSI ISA S71 04 1985 Environmental Conditions for Process Measurement and Control Systems Airborne Contaminants Physical form factor 1U rack height 1U specification Drive bays Internal Up to 8 x 2 5 inch HDD External Slim optical drive Maximum vibration Operating 0 26 Grms at 5 Hz to 350 Hz in all orientations Storage 1 88 Grms at 10 Hz to 500 Hz for 15...

Page 21: ...board Windows compliant USB equivalent or better Mouse USB equivalent or better Drives Hard Drive Tab 100 4x 300 GB 2 5 inch SAS 15K RPM hot plug drives External ports Serial One DB 9 connectors LAN 2 x RJ 45 SCSI External None USB 2 front USB2 2 back USB3 0 and 1 internal Video 2 1 Front and 1 back VGA ports Management Power related Monitoring of voltage fan µprocessor and other thermal condition...

Page 22: ...ve 2 7 3 Storage and media devices All mass storage devices are connected through SATA and PCIe SATA DVDRW drive is connected through the SATA connector on the motherboard The RAID 5 SAS controller card is located on server motherboard The standard mass storage for this platform has 4 x 300 GB 2 5 15K RPM SAS hard drives where drives 0 1 2 and 3 are in a RAID 5 configuration The option of 5th 300 ...

Page 23: ...stem configurations Any equipment configuration other than that described in this publication decertifies the Safety and EMC compliance of this product l Electromagnetic Compatibility l Safety compliance 2 8 1 Electromagnetic Compatibility The following table provides the Electromagnetic Compatibility EMC specifications Industrial Regulatory for European community Element Description Emissions EN ...

Page 24: ... Any equipment configuration other than that described in this publication decertifies the Safety and EMC compliance of this product l Electromagnetic Compatibility l Safety compliance 2 9 1 Electromagnetic Compatibility The following table provides the Electromagnetic Compatibility EMC specifications Industrial Regulatory for European community Element Description Emissions IEC 61326 1997 Basic R...

Page 25: ...the above EMC standards 2 9 2 Safety compliance The following are the light industrial regulatory product safety compliance l CSA C22 2 No 1010 1 92 R1999 and 1010 1B 97 R2001 Am 2 l IEC 61010 1 2001 2nd edition ATTENTION In the above referenced standards is a Normative Reference section citing additional standards which may apply as suited and required for product compliance 25 ...

Page 26: ... requirements Also refer to TPN System Installation Guide SW20 600 Starting the server l Before you begin 3 1 1 Before you begin Ensure that you perform the following tasks l Ensure that the cabinet is properly grounded l Unpack the platform from the box and verify the parts l Place the server on a secure surface near the cabinet to mount l Ensure that you have the necessary cables ready 3 2 Power...

Page 27: ...he thermal constraints A 1U high spaced front and side air baffles must be installed immediately above each Dell R330XL server This makes the rack space consumed by each server to be 2U Any unused rack space must have a 1U high spaced front and side air baffles installed to prevent air circulation The room ambient temperature must be kept between 10 dm and 30 dm C 50 dm to 86 dm F 3 3 1 Unused cab...

Page 28: ...e assumes that a new one meter deep equipment cabinet Honeywell model number MP C1MCB1 was shipped from the Honeywell factory with pre assembled Sliding Ready Rails The Sliding Ready Rails II kit and 1U Cable Management Arm kit are included with the purchase of Honeywell part number 51156309 100 Model No MZ PCSV63 l Honeywell server back panel connections l Installing the server l Connecting the c...

Page 29: ...ol console for your human interface pre installed in the Honeywell factory connect the KVM cable mouse and keyboard connections to the USB connectors on the rear of the server The KVM cable may have separate USB connections for the mouse and keyboard or they may be combined into one USB connector through a USB to PS 2 adapter included with the KVM cable 3 4 3 Connecting the cables To connect the c...

Page 30: ... installed 6 To complete the installation turn on the server 3 4 4 Install air duct baffles and blank panel front covers in cabinet Air duct baffles and blank panel front covers ensure that the airflow within the cabinet allows proper cooling for the servers The following image illustrates the air duct baffles and blank panel front covers used in cabinet Figure 3 2 Air Duct Baffle and Blank Panel ...

Page 31: ...to the air duct baffle and right cabinet rail using two machine screws and two external tooth washers threaded into the two clip nuts and then tighten the screws Figure 3 4 Secure Blank Panel Front Cover with Machine Screws 3 Attach the other side of the blank front panel to the left cabinet rail using two machine screws and two external tooth washers threaded into the two clip nuts and tighten th...

Page 32: ...g steps to configure a new virtual disk of RAID5 four physical disks and one hot spare To configuring RAID in Dell R330XL server 1 Turn on the server The message Power Edge Expandable RAID controller BIOS Copyright 2008 LSI Corporation Press Ctrl R to Run Configuration utility appears 2 Press CTRL R The VD Mgmt Virtual Disk Management screen appears 3 Select Controller H730 Mini 4 Press F2 to disp...

Page 33: ...ess TAB key and then move the cursor to Initialize Press the spacebar to make the selection 15 Press TAB key and then move the cursor to OK and press ENTER The computer prompts you with the message Initialization will destroy data on the virtual disk Are You Sure you want to continue 16 Press OK The message Virtual disk initialization complete appears 17 Press OK 18 Press ESC to exit The message A...

Page 34: ...iew of the Dell R330XL server These servers are provided with eight 2 5 inch hard drive chassis Figure 4 1 Front View of Dell R330XL Server The following are the explanation for the items in the images 1 Power on indicator power button 2 NMI button 3 System identification button 4 USB management port iDRAC managed USB port 5 USB connector 6 Optical drive slot 7 LCD menu buttons 8 Information tag 9...

Page 35: ... 2 Network connections Each Honeywell configured platform must be connected to an ETHERNET network l Ethernet network l ControlNet Network 4 2 1 Ethernet network ETHERNET 10 100 1000 Base T connection is the standard connection used on the Honeywell configured platform An on board dual NIC must be used for FTE configuration 4 2 2 ControlNet Network A ControlNet Network is a single coaxial trunk ca...

Page 36: ...gma PE3R Installation Instructions available at the following Honeywell Process Solutions support website https www honeywellprocess com library support Documents Experion Magma_Installation_ Instructions_HWDOC X279 en pdf 4 3 Configuring ControlNet interface card You can configure a ControlNet interface card using the Magma PE3R PCie to PCI converter box 1 For more information on the Magma PE3R P...

Page 37: ...https www honeywellprocess com library support Documents Experion Magma_Installation_ Instructions_HWDOC X279 en pdf 37 Chapter 4 Operation ...

Page 38: ... the fifth hard drive is a hot spare The configuration also contains redundant power supplies Both the hard disk drives and power supplies are hot swappable and must be of same capacity and speed You must replace only one power supply and or hard disk drive at a time in a system that is turned on Refer to the Dell documentation for detailed instructions on swapping the power supply and hard disk d...

Page 39: ...System Installing System Options Installing Drives Getting Help Jumpers Switches and Connectors I O Ports and Connectors Abbreviations and Acronyms 5 2 Adding additional memory in Dell R330XL 5 2 1 Prerequisites l Turn off the system l Disconnecting power cords and cables from the server CAUTION The DIMMs are hot to the touch for some time after the system is powered down Allow time for the DIMMs ...

Page 40: ...ver of the server Figure 5 1 Removal of Top Cover 3 The DIMM memory sockets are now exposed Figure 5 2 DIMM Memory Sockets 4 While wearing a grounded ESD wrist strap press the socket ejectors on the memory module socket down to allow the memory module to be inserted into the socket 5 Insert the memory module Figure 5 3 Installation of Memory Module 40 ...

Page 41: ...cket align with the socket ejectors on the other sockets that have memory modules installed 8 Close the top cover 9 Replace the server in the cabinet 10 Connect the power cords and cables to the back panel of the server 11 Press the Power On Off button on the server to turn on the power 5 3 Installing hot spare hard drive You can insert the hot spare hard drive when the server in on 5 3 1 To inser...

Page 42: ...rt the Hot Spare Hard Drive 5 Press the bracket on the hard drive such that it is locked in the fifth bay marked as 4 Figure 5 7 Locking of Bracket 6 The hot spare hard drive is installed in the server Figure 5 8 Spare Hard Drive Installation 5 4 Servicing Honeywell options CAUTION Do not damage the EMI gasket fingers when removing installing boards 42 ...

Page 43: ...ot Free Slot 2 NICs Standard Ethernet through two on board NICs Free Slot Free Slot Free Slot 5 5 Verifying correct BIOS settings All Honeywell systems must have the Honeywell recommended BIOS version Honeywell configures specific BIOS settings in the factory for each of the server platform configurations and these settings must not be altered The following table provides the default BIOS settings...

Page 44: ...n 2 4 or higher Memory information for Tab 51156061 100 System memory size 8 GB System memory type ECC DDR4 System memory speed 2133 MHz System memory voltage 1 20 V Video memory 16 MB System memory testing Disabled Memory operating mode Optimizer mode Memory information for Tab 51156061 200 System memory size 16 GB System memory type ECC DDR4 System memory speed 2133 MHz System memory voltage 1 2...

Page 45: ...tcher Enabled DCU IP Prefetcher Enabled Configurable TDP Nominal X2APIC Mode Disabled Number of Cores per processor All Processor 64 bit Support Yes Processor Core Speed 3 60 GHz Processor 1 Family Model Stepping 06 5E 3 Brand Intel Xeon CPU E3 1270 V5 3 60 GHz Level 2 Cache 4 X 256 KB Level 3 Cache 8 MB Number of cores 4 Microcode 0x74 45 Chapter 5 Servicing ...

Page 46: ...BIOS Boot Sequence Retry Enabled Hard disk Failover Disabled Boot sequence 1 Embedded SATA Port Optical Drive F DVD drive model number 2 Hard Drive C 3 Embedded NIC1 Port 1 Partition1 BRCM MBA Slot 0200 V17 0 1 or higher Boot option Enable Disable 1 Embedded SATA Port Optical Drive E DVD drive model number X 2 Hard disk C X 3 Integrated NIC1 Port 1 Partition1 BRCM MBA Slot 0100 V16 4 3 or higher X...

Page 47: ...led Memory mapped I O above 4 GB Disable Slot Disablement Global Slot Boot driver disable Disabled Slot 1 Enabled Slot 2 Enabled Serial communication Serial communication On without Console Redirection Serial Port Address Serial Device 1 COM1 Serial Device 2 COM2 External Serial Connector Serial Device 1 Fail Safe Baud Rate 115200 Remote Terminal Type VT100 VT220 Redirection After Boot Enabled 47 ...

Page 48: ...Management Maximum Performance Memory Frequency Maximum Performance Tubo boost Enabled C1E Disabled C states Disabled Memory refresh rate 1x Uncore Frequency Maximum Energy efficient policy Performance Number of Turbo boost enabled cores for processor 1 All Monitor Mwait Enabled 48 ...

Page 49: ... Power Recovery Last AC power recover delay Off User defined delay 60s to 240s 60 UEFI Variable Access Standard Secure boot Secure boot Disabled Secure boot policy Standard Secure boot policy summary Secure boot Custom policy setting Miscellaneous settings System Time HH MM SS System date MM DD YYYY Asset Tag Keyboard Num Lock On F1 F2 Prompt on Error Enabled Load legacy Video Option Rom Disabled ...

Page 50: ...4 GB ECC DDR4 UDIMM 2133 Mhz or better 370 ACFU 51156061 901 Expansion RAM 8GB ECC DDR4 UDIMM 2133MHz or faster 51156061 907 Hard Disk Drive 300 GB 15K RPM SAS 12 Gbps 2 5 in Hotplug Hard Drive or better 51156061 906 Rack mount Rails Ready Rails Sliding Rails With Cable Management Arm 770 BBBL 51156061 902 SMPS Dell Hot Plug Power Supply 350 W 450 AEUV 51156061 903 DVD Drive DVD RW SATA Internal 4...

Page 51: ...f any may be found in the materials accompanying the product in the documents or files accompanying such third party materials in a file named third_ party_licenses on the media containing the product or at http www honeywell com ps thirdpartylicenses Documentation feedback You can find the most up to date documents on the Honeywell Process Solutions support website at http www honeywellprocess co...

Page 52: ...te https www honeywellprocess com en US contact us customer support contacts Pages default aspx Training classes Honeywell holds technical training classes that are taught by process control systems experts For more information about these classes contact your Honeywell representative or see http www automationcollege com 52 ...