Chapter 2 - Planning
Operating temperature
+10° to +35° C (50° to 95° F) with a maximum
temperature gradation of 10° per hour .
Note: for Altitudes above 2950 feet , the maximum
operating temperature is de-rated 1°F/550ft.
All temperature ratings shown are for sea level. An
altitude de-rating of 1°C per 300 m (1.8°F per 1,000
ft) to 3048 m (10,000 ft) is applicable. No direct
sunlight allowed.
Shipping temperature
-30°C to 50°C (-22°F to 122°F)
Storage temperature
-40°C to 65°C (-40°F to 149°F)
Maximum wet bulb
temperature
28°C (82.4°F)
ATTENTION
All temperature ratings described
previously are for sea level. An altitude
derating of 1°C per 300 m (1.8°F per 1,000
ft) to 3048 m (10,000 ft) is applicable. Direct
sunlight is not allowed.
Operating humidity
10% to 80% (non-condensing) with a maximum
humidity gradation of 10% per hour and 29°C
(84.2°F) maximum dew point.
Storage humidity
5% to 95% (non-condensing) ) with a maximum
humidity gradation of 10% per hour and with 33°C
(91°F) maximum dew point.
Note: Atmosphere must be non-condensing at all
times.
ATTENTION
Storing maximum humidity of 95% is based
on a maximum temperature of 45°C
(113°F). Altitude maximum for storage
corresponds to a pressure minimum of 70
KPa.
Airborne Contaminants
Airborne Contaminants < 300 angstroms/month
Copper Reactivity Level
Copper Reactivity Level < 3 mm3/m3 parts per billion
pS Gas concentration
pS Gas concentration < 10 mm3/m3 parts per billion
- 19 -