Rack Installation Guide
9
Removing the Rack Doors
See the procedures for removing doors in the documentation provided with your rack cabinet.
CAUTION:
Because of the size and weight of the rack cabinet doors, never attempt to remove or install them
by yourself.
CAUTION:
Store the two doors where they will not injure someone if the doors accidently fall over.
Marking the Rack
For a 5-U system, you must allow 5 U (8.75 inches) of vertical space for each system you install in the rack
(see Figure 1-2).
Rack cabinets that meet EIA-310 standards have an alternating pattern of three holes per rack unit with
center-to-center hole spacing (beginning at the top hole of a 1-U space) of 15.9 mm, 15.9 mm, and 12.7 mm
(0.625 inch, 0.625 inch, and 0.5 inch) for the front and back vertical rails (see Figure 1-2). Rack cabinets may
have round or square holes.
NOTE:
The vertical rails may be marked by horizontal lines and numbers in 1-U increments. If you want, you can
make a note of the number marking on the rack’s vertical rail. It is not necessary to mark or place tape on the rack.
NOTE:
Your rack may already be marked and not require this procedure.
Figure 1-2.
One Rack Unit
CAUTION:
If you are installing more than one system, install the sliding rail assemblies so that the first system
is installed in the lowest available position in the rack.
1 U (44 mm or 1.75 inches)
12.7 mm (0.5 inch)
15.9 mm (0.625 inch)
15.9 mm (0.625 inch)
12.7 mm (0.5 inch)
Summary of Contents for PowerEdge 2900
Page 2: ......
Page 3: ...Rack Installation Guide ...
Page 6: ...4 Contents ...
Page 23: ...Guide d installation du rack ...
Page 26: ...24 Sommaire ...
Page 44: ...42 Guide d installation du rack ...
Page 45: ...Rack Installationsanleitung ...
Page 48: ...46 Inhalt ...
Page 67: ...ラック取り付けガイド ...
Page 70: ...68 目次 ...
Page 88: ...86 ラック取り付けガイド ...
Page 89: ...Guía de instalación del rack ...
Page 92: ...90 Contenido ...
Page 110: ...108 Guía de instalación del rack ...