30
Dell EMC Connectrix EC-1700 Cabinet Installation and Setup Manual
Installation and Setup
Planning overview
This section contains the following information:
◆
“Service clearances” on page 30
◆
“Floor load-bearing requirements” on page 31
◆
“Installation guidelines” on page 33
Service clearances
IMPORTANT
The hardware enclosure contains no user-serviceable parts, so it
should not be moved or opened for any reason by untrained
persons. If the hardware needs to be relocated or repaired, only
qualified personnel familiar with safety procedures for electrical
equipment and Dell EMC hardware should access components
inside the unit or move the unit.
Most Dell EMC cabinets ventilate from front to back; you must
provide adequate clearance to service and cool the system (
Figure 7
EC-1700 cabinet area clearances