Dim Label
Description
l
f = recommended minimum of 3" (7.62cm)
l
g = rear rack post width (if any)
l
pw + ½" (1.3cm) ≤ f+g
j
≥ 6" (15.24cm) is a requirement.
Distance between rear-facing surface of vertical PDU and the rack post or any other parallel
surface that may interfere with the power cables.
Note: Dimension k is dependent on this value.
k
= min depth: b+c
Where:
l
j ≥ 6" (15.24cm) is a requirement.
l
IF j is ≥ 6" (15.24cm), min rack depth = 43" (109.2cm).
l
IF j is < 6" (15.24cm), min rack depth = 43" (109.2cm) + distance required to make j ≥
6" (15.24cm).
pw
= PDU width
Third Party Racking Option