R290
Important
We assume no responsibility for the use of contaminated
refrigerant. Damage resulting from the use of
contaminated refrigerant is the sole responsibility of the
servicing company.
Connections
1. Suction side of the compressor through the suction
service valve.
2. Discharge side of the compressor through the
discharge service valve.
Charging Procedures
Important
The charge is critical on all Reach-In units. Use a scale or a
charging cylinder to ensure the proper charge is installed.
1. Disconnect power to the unit.
2. Close the vacuum pump valve, the low side service
valve, and the low side manifold gauge valve.
3. Open the high side manifold gauge valve and the high
side service valve.
4. Open the charging cylinder and add the proper
refrigerant charge (shown on nameplate) through the
discharge service valve.
5. Let the system “settle” for 2 to 3 minutes.
6. Connect power up the unit.
7. Close the high side valve on the manifold gauge set.
Add any remaining vapor charge through the suction
service valve (if necessary).
NOTE: Manifold gauges must be removed properly to
ensure that no refrigerant contamination or loss occurs.
8. Make sure that all the vapor in the charging hoses
is drawn into the Reach-In before disconnecting the
charging hoses.
A. Run the Reach-In cooling mode.
B. Close the high side service valve at the Reach-In.
C. Open the low side service valve at the Reach-In.
D. Open the high and low side valves on the manifold
gauge set. Any refrigerant in the lines will be pulled
into the low side of the system.
E. Allow the pressures to equalize while the Reach-In
is running.
F. Close the low side service valve at the Reach-In.
G. Remove the hoses from the Reach-In and install
the caps.
Section 8
Refrigeration
Summary of Contents for Specification Line GA Series
Page 6: ...6 Part Number GA_SM 08 18 General Information Section 1 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 20: ...20 Part Number GA_SM 08 18 Installation Section 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 36: ...36 Part Number GA_SM 08 18 Troubleshooting Section 5 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 48: ...48 Part Number GA_SM 08 18 Control Section 6 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 94: ...94 Part Number GA_SM 08 18 Refrigeration Section 8 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 102: ...102 Part Number GA_SM 08 18 Diagrams Section 9 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 103: ......