Air Curtain Refrigerator Service and Installation Manual

9

For customer service, call (800) 733-8829 or (800) 733-8948, Fax (989) 773-3210, www.delfield.com

Defrost Interval  

dFin 

Type of defrost interval  

TdAy – time -of-day 
setpoint  
CPrn – compressor run 
time  
tdEF – temperature 
initiated defrost  

Minimum 
Compressor Off 
Time 

CoFF 

Minimum time that the 
compressor will remain turned off  

Range: from 0 to 15 
min 

Minimum 
Compressor On 
Time 

Con 

Minimum time that the 
compressor will remain turned on  

Range: from 0 to 15 
min 

Alarm Delay 

ALrd 

Time delay before the alarm goes 
off after the temperature fall off 
the two alarm setpoints  

Range: from 0 to 59 
min 

30 

Compressor Run 
Time 

CPrn 

Time the compressor will run 
between defrosts  

 

 

Number of 
Defrosts 

nodF 

Number of  defrosts per day  

From 0 to 8 (0 means 1 
defrost every 28 
hours) 

Defrost Start 
Time 

dEF1-8 

Start time of each defrost  

 

Defrost Duration  

DEFd 

Defrost duration time (back -up 
for defrost termination 
temperature)  

Range: from 0 min to 4 
hours 
 

45

Fan Delay 

FAnd 

Delay time for the fan after 
defrost(back -up for fan cut -in 
temperature)  

Range: from 0 to 59 
min 

Pump Down 

Pudn 

Pump down duration  

Range: from 0 to 59 
min 

Drip Time 

driP 

Drip time duration  

Range: from 0 to 59 
min 

Setpoint 
Differential  

diF° 

Cut-in temperature differential  
Note: cut -in is cut-out plus 
differential  

Range: from 1 to 25  

Defrost 
Termination 
Temperature

Defrost 
Termination 
Temperature

Defrost 
Initiated 
Temperature

 

dEF° 

Temperature in the evaporator 
that will terminate the defrost 
cycle 

45°F 

Fan Cut-In 
Temperature  

FAn° 

Temperature in the evaporator 
that will turn the fan on after 
defrost  

Range: from -40 to 
60°F or -40 to 23°C 

30°F 

Low Temperature 
Alarm 

ALLo 

Low temperature setpoint that 
will make the alarm do off and 
the error message appear on the 
display 

Range: from -40 to 
60°F or -40 to 23°C 

25°F 

tdEF

tdEF 

Temperature that will initiate 
a defrost  cycle

Range: from -40 to 40°F 
or -40 to 4°C 

10°F 

Range: from 0 to 75 °F 
or -18 to 25°C 
 

ERC2 Control Instructions, 

continued

Summary of Contents for ACR-26S

Page 1: ...d Installation Manual Please read this manual completely before attempting to install this equipment Notify carrier of damage Inspect all components immediately February 2013 Important Information Rea...

Page 2: ...e Is Not Intended For Use By Persons Who Lack Experience Or Knowledge Unless They Have Been Given Supervision Or Instruction Concerning Use Of The Appliance By A Person Responsible For Their Safety WA...

Page 3: ...he contents with the carrier 3 In the event that the exterior is not damaged yet upon opening there is concealed damage to the equipment notify the carrier Notification should be made verbally as well...

Page 4: ...g for parts or service A complete list of authorized Delfield parts depots can be found on www delfield com 2013 The Delfield Company All rights reserved Reproduction without written permission is pro...

Page 5: ...ge be sure it is connected to the proper power source A protected circuit of the correct voltage and amperage must be run for connection of the line cord or permanent connection to the unit Reversing...

Page 6: ...ry thoroughly Routine cleaning of stainless steel can be done with soap and water Extreme stains or grease should be cleaned with a non abrasive cleaner and plastic scrub pad Always rub with the grain...

Page 7: ...rs Three buttons are used for the programming SET UP and DOWN Fig 2 Display Lay out Follow these steps to change time of day and setpoint temperature First Level Step 1 Press and hold set for 5 second...

Page 8: ...changed in the Second Level of programming as well as their options and ranges Parameter Display Symbol Description Range Options Delfield Settings Display Status dSPL Information shown on the displa...

Page 9: ...ost duration time back up for defrost termination temperature Range from 0 min to 4 hours 45 Fan Delay FAnd Delay time for the fan after defrost back up for fan cut in temperature Range from 0 to 59 m...

Page 10: ...Press SET again Press Up or DOWN until the correct time appears on the display Press SET to accept the new time Press DOWN twice to exit the programming mode Example 2 To set one defrost a day at 11...

Page 11: ...reset the display For Codes 3 and 4 press the UP or DOWN button on the display to reset the error message If the display still shows the message the sensor must be replaced The Error Codes 6 and 7 wi...

Page 12: ...Air Curtain Refrigerator Service and Installation Manual For customer service call 800 733 8829 or 800 733 8948 Fax 989 773 3210 www delfield com 12 ACR 26S Wiring Diagram...

Page 13: ...0003 Pan Drip Coil ACR 26S 2194577 Probe ERC2 Control 2190154 Switch Rocker 20A 125V 3516084 Valve Exp 1 2Ton R 404A 000 187 0040 Door Assembly ACR 26S RT 1701147 Gasket Dr 45 50x23 81 000 BJ4 0030 Hi...

Page 14: ...Air Curtain Refrigerator Service and Installation Manual For customer service call 800 733 8829 or 800 733 8948 Fax 989 773 3210 www delfield com 14 Notes...

Page 15: ...Air Curtain Refrigerator Service and Installation Manual 15 For customer service call 800 733 8829 or 800 733 8948 Fax 989 773 3210 www delfield com Notes...

Page 16: ...2 13 9291461 Delfield Thank you for choosing Delfield Help is a phone call away Help our team of professional courteous customer service reps by having your model number and serial number available at...

Reviews: