RDL150 RS485/RS232

4.

RS485 Interface

Most RS485-buses require termination resistors across the conductor pair. The need for termina-
tion has to be proofed for each installation. Especially for fast transitions, high data rates or long
cables the resistors are absolutely necessary. Only both ends of the main cable require termination
resistors, additional resistors excessively loads the driver. The resistor value matches the cable's
differential-mode characteristic impedance (100-120 Ohm).

At the RS485-bus you need a controller with fail-safe biasing, meaning a pull-up and a pull-down
resistor on the cable. The fail-safe biasing provides a known state in which there is no active
driver on the bus and therefore it is essential, independent from data rates and length of the cable.

(Bus with RS485 interface)

Technical data (for baud rates up to 100 kHz):

Max. cable length:

1200m (4000 feet)

Max. stub length

:

because of reflections stubs should be as short as possible
Exceptions allow a length up to 5 m (16 feet)

Recommendation
for the cable:

twisted pair, cable-cross-section at least 0,22mm² (AWG 24)
differential-mode characteristic impedance 100-120 Ohm

Summary of Contents for RDL150 RS232

Page 1: ...V17 08 05 RDL150 RS485 RS232 Wiring Installation Instructions...

Page 2: ...echanical photocopying recording or otherwise without prior written permission of deister electronic GmbH deister electronic GmbH reserves the right to make changes to any and all parts of this docu m...

Page 3: ...ith RS485 6 3 1 Connection RDL 150 with RS232 6 4 RS485 Interface 7 5 Mechanical Dimensions 8 5 1 Rear view opened housing 9 5 2 LED explanation 10 5 3 Easy Trim Function 11 6 Installation Instruction...

Page 4: ...o be connected directly to a PC processor or controller 1 2 Applications The reader was especially designed for applications where it is necessary to read and write several transponders at the same ti...

Page 5: ...ppressor diode protection on data lines trigger input and switching output Electrical connection 1m shielded cable open wire shield is not internally connected Operating frequency 13 56 MHz Read write...

Page 6: ...nternal connected with GND_IN 3 Connection RDL150 with RS485 3 1 Connection RDL150 with RS232 deister electronic GmbH 30890 Barsinghausen Germany 6 RDL150 RS485 RS232 V19 07 04 Color of cable Signal F...

Page 7: ...ntial mode characteristic impedance 100 120 Ohm At the RS485 bus you need a controller with fail safe biasing meaning a pull up and a pull down resistor on the cable The fail safe biasing provides a k...

Page 8: ...V19 07 04 5 Mechanical Dimensions All dimensions in mm Status red LED displays errors and error telegrams or valid data Read green LED displays succesful reading of a transponder Power yellow LED alw...

Page 9: ...deister electronic GmbH 30890 Barsinghausen Germany 9 V19 07 04 RDL150 RS485 RS232 5 1 Rear view opened Housing The switches S1 S5 and S7 will be explained in chapter 4 3...

Page 10: ...uring write instructions 3 Red LED Status indicator Displays error telegrams The LED activates for about 200ms on the following events Communication error telegrams Non executable commands If the read...

Page 11: ...st be turned to the right Yellow LED The rotatable switch S5 must be turned to the left Green LED The setting of the rotatable switch S5 matched the best performance It could be possible that there ar...

Page 12: ...wing distance between reader and interference source the influence decreases LCD monitors have a minimal influence on the read range In particular the reader should be mounted on non metallic material...

Page 13: ...tion of separation distances vertical and back to back 1 Mount all readers before tuning any of the readers 2 Ensure that the back to back distance is at least one meter Note 1 If a metal plate is ins...

Page 14: ...ding Firmware To perform a firmware update with deFlash please follow the steps below Connect reader serial interface with PC then plug in power supply Start deFlash exe Select the COM Port the reader...

Page 15: ...tivated Wait until display shows Programming finished Version XXXXXX Exit program If programming fails repeat procedure as described above If repetition fails again please disconnect power supply of r...

Page 16: ...le protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used...

Page 17: ...deister electronic GmbH 30890 Barsinghausen Germany 17 V19 07 04 RDL150 RS485 RS232 Notes...

Page 18: ...deister electronic GmbH 30890 Barsinghausen Germany 18 RDL150 RS485 RS232 V19 07 04 Notes...

Page 19: ...deister electronic GmbH 30890 Barsinghausen Germany 19 V19 07 04 RDL150 RS485 RS232 Notes...

Page 20: ...lgium Luxemburg deister electronic office Business Park E 19 Battelsesteenweg 455 A 2800 Mechelen Tel 32 0 15 28 09 68 Fax 32 0 15 28 09 71 info benelux deister com The Netherlands deister electronic...

Reviews: