Cable connection 

The wind sensor is supplied with 2 metres fixed cable. From factory the cable is connected to the 

sensor  via  a  waterproof  gland,  and  this  must  not  be  replaced  by  another  cable;  the  cable  is 

extended by using a standard connection box or the optional IP67 connector kit for WSS. 

 

In  order  to  protect  the  wind  sensor  and  the  personnel  in  the  best  possible  way  from  lightning 

strokes, use a lightning rod installed with the tip at least one metre above the wind sensor. The 

lightning rod must be properly grounded in compliance with all applicable safety regulations. The 

wind sensor cable screen and the installation cable screen must be connected. 

 

For further protection of the cable between the wind sensor and the connection box, as well as the 

installation cable between the connection box and the interface box, it is recommended to use a 

metal  conduit  pipe.  If  the  instrument  is  installed  in  a  metal  panel,  this  panel  has  to  be  carefully 

earthed, as well as the instrument itself. 

 

Installation cable, e.g. UL2464 1 AE,  4  x  0.75mm

2

  screened,  max.  300m,  and  max. 

70nF capacity between the signal conductors. Suitable extension cable is available from DEIF. 

Connection of the WSS wind sensor 
Cable colour 

Function 

Note 

Black 

Supply voltage  - 

30V DC supply for the WSS wind sensor 

Red 

Orange 

RS485 comm.  A 

Wind speed and direction data output 

Brown 

Shield 

Cable shield 

Shield is  connected  to  the  stainless  steel  tap 

inside the WSS 

Connection of the WSS interface box WSI 
Pin no. 

Function 

Note 

Supply voltage  - 

24V DC (1.25A) supply for the interface box 

 

NC 

 

RS485 comm.  A 

Wind speed and direction data from the wind 

sensor  

See IMPORTANT note! 

GND 

Power supply 

out 

30V DC supply for the wind sensor 

NC 

10 

Wind speed 

TTL out 

Wind speed and direction data to the display 

type WSDI 

11 

Direction 

TTL out 

12 

Common 

GND 

13 

 

NC 

Do not connect 

14 

 

NC 

15 

 

NC 

 

 

IMPORTANT! 

The WSS stainless steel mounting base shall be connected to the ship’s earth 

cable (or steel hull).  

Summary of Contents for WSDI

Page 1: ...ad out of wind direction and wind speed NMEA data output 1 3 displays per sensor Based on ultrasonic principle no moving parts WSS version has a built in automatically activated heating element to pre...

Page 2: ...OUNTING AND CONNECTING THE WIND SENSOR 6 PLACING OF WIND SENSOR 6 CABLE CONNECTION 7 4 CONFIGURATION OF THE DISPLAY 9 COMMUNICATION TYPE NMEA 9 READ OUT OF WIND DIRECTION 9 AUX SUPPLY FOR THE DISPLAY...

Page 3: ...n be measured The wind sensor is available in two versions The WSS with a built in heater which will automatically engage when risk of icing occurs during low temperatures The WSS L without the heater...

Page 4: ...on the button decreases the light intensity by one level correspondingly The MODE key is used to switch measuring mode which enables reading of the measurements either in m s or in KTS The selected mo...

Page 5: ...e dish washer soap Avoid paint on the plastic parts of the wind sensor especially on the 3 ultrasonic sensors as paint will prevent correct function measurement of wind speed and wind direction Make s...

Page 6: ...e actual undisturbed wind speed and wind direction The wind sensor is intended for installation on a vertical socket or a tube using the tap mounted on the wind sensor on delivery See the drawing belo...

Page 7: ...conduit pipe If the instrument is installed in a metal panel this panel has to be carefully earthed as well as the instrument itself Installation cable e g UL2464 18AWG4C AE 4 x 0 75mm 2 screened max...

Page 8: ...cable Male connector Connector pin no WSS extension cable xx meters Female connector Signal comments Black 1 Black 30V DC Supply for WSS WSS L Red 2 Red Orange 3 Orange RS485 Comm from WSS WSS L Brown...

Page 9: ...display is adjusted by 180 meaning 360 pointing astern of the ship This function is activated by short circuiting the two pins at position 3 on JP1 Please notice that the 180 adjusted wind indication...

Page 10: ...f 19 Change from 110V AC to 220V AC by removing the jumpers across 1 and remounting the jumper across 2 Change from 220V AC to 110V AC by mounting the 2 jumpers across 1 and removing the jumper across...

Page 11: ...external dimmer and read out of m s or KTS in the display 2 0V Input from WSS interface box Terminal 12 on the interface box WSI 3 Wind speed Terminal 10 on the interface box WSI 4 Direction Terminal...

Page 12: ...isplay housing is then removed and the defective fuse is replaced Flashing display If the aux supply voltage is less than the nominal voltage 20 the voltage for the built in processor is inadequate an...

Page 13: ...the above the fault is related to the cable Cable failure If the read out of the wind speed is zero and the direction is indicated at 0 90 180 270 every 0 5 second the fault is probably a cable break...

Page 14: ...sumption 6W Weight 0 8kg Dimensions See drawing in chapter 7 of this manual NMEA 0183 Version 1 5 or version 2 x 3 0 Transmission speed 4800 Baud Number of bits 8 Number of parity bits 0 Number of sto...

Page 15: ...connected Applicable would be a PC with the following configuration Transmission speed 4800 Baud Number of data bits 8 Parity bits None Number of stop bits None Number of connected receivers to the N...

Page 16: ...eed and Direction Indicator WSDI m s kts m s kts 1 2 3 4 5 A B 9 10 11 TO WSS INTERFACE BOX NMEA 0183 LISTENER CABLE 2x0 75mm TWISTED PAIR SCREENED EXTERNAL CONTROL IF USED 5 0V SPEED DIRECTION SIGNAL...

Page 17: ...ay WSDI WSS WSS interface box 3 4 2 D wind Direction S wind Speed The WSS box has to be mounted indoor recommended is close to the indicator 1 2 3 4 5 A B 9 10 11 220V AC EARTH 5V 0V wind Speed DIRECT...

Page 18: ...B 9 10 11 MODE DIRECTION SPEED 0V 5V 5V 0V SPEED DIRECTION SIGNAL RETURN MODE 11 10 9 B A 5 4 3 2 1 SUPPLY COMMON OR INDIVIDUAL LISTENER ACCORDING TO NMEA 0183 EXTERNAL CONTROL SUPPLY STANDARD Displa...

Page 19: ...WSI WSDI WSS or WSS L User s Manual DEIF A S Page 19 of 19 Interface box DEIF A S reserves the right to change any of the above 85 0 75 0 110 0 61 0 4 5 99 7 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1...

Reviews: