background image

DM-4 Land/DM-4 Marine 

4189340469B 

Replacement Instructions, PCM 4.X

 

 

 

DEIF A/S

  

Page 5 of 5 

Software: 
Please observe the software version number etc. (display reading). 
 

 

- Project number 
- Version number 
- Revision number 

 

Read all settings (timers and limits) before exchanging the module. 
 

 

 

 

-  Switch all equipment into switchboard control 
-  Remove the power supply from the defective DGU 
-  Remove other connections/plugs on the PCM 
-  Exchange the module after securing the correct settings of the jumpers and rotation switch 
-  Connect the plugs and power supply again 
-  Download the application software to the unit  
-  Download the parameter settings by means of the utility software and check these  
-  Make a test to secure that the system works as predetermined 

 

Address switch/jumpers on the PCM module

ID-switch

S5

 

 
 
If the dedicated software is not present, then contact DEIF to have the software sent by e-mail. 
  
Please refer to the manual for the utility software for further explanations regarding this software. 
 
 
 
 

DEIF A/S reserves the right to change any of the above.

 