DM-4 Land/DM-4 Marine
4189340469B
Replacement Instructions, PCM 4.X
DEIF A/S
Page 5 of 5
Software:
Please observe the software version number etc. (display reading).
- Project number
- Version number
- Revision number
Read all settings (timers and limits) before exchanging the module.
- Switch all equipment into switchboard control
- Remove the power supply from the defective DGU
- Remove other connections/plugs on the PCM
- Exchange the module after securing the correct settings of the jumpers and rotation switch
- Connect the plugs and power supply again
- Download the application software to the unit
- Download the parameter settings by means of the utility software and check these
- Make a test to secure that the system works as predetermined
Address switch/jumpers on the PCM module
ID-switch
S5
If the dedicated software is not present, then contact DEIF to have the software sent by e-mail.
Please refer to the manual for the utility software for further explanations regarding this software.
DEIF A/S reserves the right to change any of the above.