MTR-3
Installation Instructions
DEIF A/S
Page 41 of 51
Register table for the actual measurements (VERSION 2)
Parameter
PLC
Modbus Reading
Address
Address
Function
Type
Start
End
Start
End
THD HARMONIC DATA
U1 THD%
300639
300639
639
639
04
T16
U2 THD%
300640
300640
640
640
04
T16
U3 THD%
300641
300641
641
641
04
T16
U12 THD%
300642
300642
642
642
04
T16
U23 THD%
300643
300643
643
643
04
T16
U31 THD%
300644
300644
644
644
04
T16
I1 THD%
300645
300645
645
645
04
T16
I2 THD%
300646
300646
646
646
04
T16
I3 THD%
300647
300647
647
647
04
T16
Parameter
PLC
Modbus reading
Address
Address
Function
Type
Start
End
Start
End
DYNAMIC DEMAND VALUES
Time Into Period (minutes)
300175
300175
174
174
04
T1
I1
300176
300177
175
176
04
T5
I2
300178
300179
177
178
04
T5
I3
300180
300181
179
180
04
T5
Apparent Power Total (St)
300182
300183
181
182
04
T5
Active Power Total (Pt) -
(positive)
300184
300185
183
184
04
T6
Active Power Total (Pt) -
(negative)
300186
300187
185
186
04
T6
Reactive Power Total (Qt) - L
300188
300189
187
188
04
T6
Reactive Power Total (Qt) - C
300190
300191
189
190
04
T6
MAX DEMAND SINCE LAST RESET
I1
300208
300209
207
208
04
T5
I2
300214
300215
213
214
04
T5
I3
300220
300221
219
220
04
T5
Apparent Power Total (St)
300226
300227
225
226
04
T5
Active Power Total (Pt) -
(positive)
300232
300233
231
232
04
T6
Active Power Total (Pt) -
(negative)
300238
300239
237
238
04
T6
Reactive Power Total (Qt) - L
300244
300245
243
244
04
T6
Reactive Power Total (Qt) - C
300250
300251
249
250
04
T6