Figure 1
Design of the
HVI
®
Conductor
as assembled conductor with
factory-mounted head piece
sealing end range
head piece
EB connection element (fixed)
HVI
®
Conductor
with special sheath
earth connection element (detachable)
HVI
®
Conductor I
Part No. 819 020
Colour: black
Part No. 819 023
Colour: grey
HVI
®
Conductor II
Part No. 819 021
Colour: black
Part No. 819 024
Colour: grey
HVI
®
Conductor III
Part No. 819 022
Colour: black
Part No. 819 025
Colour: grey
sealing end range
head piece
EB connection element (fixed)
HVI
®
Conductor
with special sheath
head piece
sealing end range
sealing end range
head piece
EB connection element (fixed)
HVI
®
Conductor
with special sheath
connection element
(not fixed)
sealing end range
EB connection element (not fixed)
Conductor
Part No. Field of application
HVI
®
Conductor I
819 020 Is used for connecting the air-termination system of the
with head piece / sealing end 819 023 external lightning protection system directly to the
and earth connection element
earth-termination system of the building (Fig. 3, page 5)
HVI
®
Conductor II
819 021 Is used for connecting e.g. several parts of the installation
with two head pieces / sealing 819 024 to be protected jointly to the earth-termination system
ends
of the building via an "isolated ring conductor"
(see Fig. 5, page 9, "isolated ring conductor")
HVI
®
Conductor III
819 022 Conductor with a fixed sealing end and a sealing end
with head piece and
819 025 to be adjusted on site is typically used where the total
unassembled
conductor length cannot be exactly defined during the
connection element
design stage of the installation.
HVI
®
Conductor III
can be used like
HVI
®
Conductor II
.
HVI
®
Conductor III
can be shortened, but not extended.
Table 2
Design of the
HVI
®
Conductor
- Fields of application of the assembled conductor