1811_MO_1012_DE_GB_063061
Outer sheath
Colour
black
grey
RAL 9011
RAL 7035
Equivalent
Air
≤
75 cm
separation distance
Solid materials
≤
150 cm
Outer diameter
20 mm
23 mm
Minimum bending radius
200 mm
230 mm
Permanent temperature range (in case of permanent installation)
-30° bis +70°C
Ambient temperature and conductor temperature
-5° bis +40°C
(during installation and processing)
Maximum tensile load
950 N
Inner conductor Cu solid / stranded
19 mm
²
1. Installation and use
The
HVI
®
Conductor
is a high-voltage-resistant, insulated down conductor with a voltage-controlled
outer sheath.
It is typically used as insulated down conductor in lightning protection systems to maintain the separation
distance in accordance with IEC 62305 Part 3 (DIN EN 62305-3) (VDE 0185-305-3). At first, the separation
distance has to be calculated as explained in IEC 62305 Part 3 (DIN EN 62305-3 (VDE 0185-305-3),
Subclause 6.3, with a material factor of km = 1 in air, or km = 0.5 for solid material. It has to be tested
if this calculated separation distance can be realised with the equivalent separation distance of the
HVI
®
Conductor
(see technical data, Table 1):
calculated separation distance
≤
equivalent separation distance.
If this is not the case, measures according to section 9 or 10 have to be taken.
The length for calculating the separation distance
“s”
has to be measured from the head piece (see Fig.
1, page 3) to the next level of lightning equipotential bonding, e.g. the earth-termination system.
The programme of HVI Conductor system components consists of a
HVI
®
Conductor
and a
product range of connecting and fixing elements for this conductor.
The design and installation of
HVI
®
Conductors
require special know-how.
Table 1
Technical data of the
HVI
®
Conductor