DEGA UPA III User Manual Download Page 11

 

11 

The entries TMP1 and TMP2 change the temperature value of the external sensor at which an alarm occurs. Pressing LEFT 
decreases the temperature and pressing RIGHT increases the temperature. Press ENTER to confirm the change. 

Attention, 

the 

temperature alarm value changes immediately after pressing LEFT or RIGHT. If the immediate temperature value exceeds the 
alarm value, 

it will change the output state

.  

The entries ALM1 to ALM4 are used to set the alarm of the transmitters. Press ENTER to browse the alarms by using LEFT and 
RIGHT. Each channel shows the size of the alarm and the segment 1-4 shines, based on the selected alarm. Press ENTER again 
to move to the edit mode. The segment 1-4 blinks and we can set the value by using LEFT and RIGHT. Pressing ENTER again will 
end the edit mode. 

Attention, analog channel

 value changes are immediate and so are the output changes. The changes are 

saved after pressing ENTER. 
The entry CALI serves for calibration of the digital transmitters. LEFT and RIGHT changes the displayed channel and ENTER 

selects the channel (displayed 

). Moving to the entry NEXT and pressing ENTER goes to zero-calibration of the selected 

transmitters. This mode displays a minimal AD conversion value on the main segment. The secondary segments display the 
maximal value. The oxygen detector is an exception, which always detects a 0 value in the zero-mode. By using LEFT and 
RIGHT it's possible to check the detected value of every selected transmitter and eventually wait for it to drop. Press NEXT to 
move to the calibration range mode. Inletting a calibration gas to the transmitter will start a concentration measuring of the 
calibration gas. The highest value of the AD conversion is displayed on the main display and the lowest value is displayed on 
the secondary segments. If we are satisfied with the values, we can move on to the next part by clicking NEXT, which will bring 
us to the settings of the calibration interval. This can be changed with LEFT and RIGHT and using ENTER will confirm the 
selection. In the final part of this whole process select either YES for saving the values into the transmitters, or no for finishing 
the calibration without saving the values. 
 

Controller testing menu TEST 

RELE 

Setting the relay output 

TRAN  Simulation of the measured values 
_RST 

Controller restart 

EXIT 

Returns to a higher menu level 

 
The entry RELE is used for direct setting of the controller outputs. Entering this entry saves the current state of the outputs, 
which are later modified by the user. The controller outputs (RE1 to RE10, LIGH, SOUN, _HV) can be browsed with LEFT and 
RIGHT and pressing ENTER will switch the output state. The outputs will remain in these settings for as long until we don't 
press ENTER on the last EXIT entry. That will restore the output state, which existed before the user change. 
The entry TRAN is similar to the entry RELE, except for the fact that the user sets the concentrations on the given channel. Use 
LEFT and RIGHT to select a channel and then press ENTER to enter the edit mode. Here we can use the arrows to change the 
concentration ranging from minimal to maximal value of the configured transmitter. The controller reacts to this set 
concentration as if it was directly measured, which leads to occurring alarms and switching outputs.   
The entry _RST resets the controller. 

Service Menu SERV 

The entry SERV ALL SENS makes the controler go into service mode. The communication with transmitter is stopped and the 
outputs are set in the last known state. Use LEFT and RIGHT to set the servise interval in a range of 1 to 24 hours. Press ENTER 
to start it's own regime. 
The main segments display a countdown of the set interval in seconds and the malfunction segments (key symbol) blinks. 
After the countdown finishes, the controller returns to the detection mode. This regime can be interrupted anytime by 
pressing ENTER.  
The entry SERV SEL SENS causes a blockage of any transmitter until the next restart of the controller. Use LEFT and RIGHT to 
select a transmitter and ENTER to block/unblock. Blocked transmitters are indicated with an inscription DIS on the main 
segments. 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for UPA III

Page 1: ...ny form without the prior permission of DEGA CZ s r o is prohibited DEGA CZ s r o reserves the right to alter the specifications of the hardware and software described in this manual at any time and without prior notice DEGA CZ s r o bears no liable for any damage resulting from use of this device ...

Page 2: ... past alarms 9 9 Automatic adjustment of the 0 point 9 10 Menu 9 History Menu HIST 10 Information menu INFO 10 Configuration menu CONF 10 Controller testing menu TEST 11 Service Menu SERV 11 Maintenance 12 1 Operation Maintenance 12 2 Replacement of the battery 12 Attachments 13 1 Table of error codes 13 General warranty terms and conditions 14 For your safety Beware of static electricity Electron...

Page 3: ... 25 mm max 100 m Cable for connecting signalization a pushbutton cable 2 x 1mm Output USB for PC configuration RS485 protocol DEGA or MODBUS on request for the host system PLC PC 10x switching relays 250 V 10 A 2x outupt for visual and acoustic alarms max load see chapter Assembling and connecting the wiring paragraph 6 Communication speed of RS485 9 6 kB Functional safety EN61508 SIL 1 Dimensions...

Page 4: ...e suppy voltage 22 26V Terminal block relay RE8 RE10 Fuse T400mA Auxiliary input output 24V DC Power supply terminal block 230VAC Temperature sensor terminal block Acoustic alarm lay key terminal block Flooding sensor terminal block Acoustic alarm terminal block Bus temrinal block 1 for digital transmitters Bus temrinal block 0 for digital transmitters RS485 for the host system Analog inputs Optic...

Page 5: ...e cover of the case and lock the controller by using the handle 2 Connecting a transmitter via current loop Connect one transmitter on each channel of the controller 3 Connecting a transmitter via RS485 It is possible to connect up to 16 transmitters on each controller input depending on their electrical distance from the controller Wiring installation for RS485 Wiring must be done using bus topol...

Page 6: ... the supply voltage and the maximum current load Supply voltage 230V AC The highest current load of the controller is 1 4A This current serves to power the connected transmitters and the visual and acoustic alarms which are connected to the terminal blocks LIGHT_SIG and SOUND_SIG Example There are 4 transmitters connected to the controller with a consuption of 60 mA each The remaining 1 16 A I 140...

Page 7: ...imru můžeme regulovat výstupní napětí zdroje v rozsahu 22 26V V případě že jsou snímače připojeny na velkou vzdálenost může být pro správnou funkci nutné zvýšit napájecí napětí Controls The control panel is equipped with a segmented LCD display and can be controlled using the LEFT RIGHT and ENTER buttons In Basic mode the controller displays the concentration and the states of the configured chann...

Page 8: ...cation or an evnetual sensor malfunction If the displayed channel is digital 1 to 32 the adress of the connected sensor is also displayed Connected analog transmitters have a range of 41 to 48 The controller sequentially switches the configured channels in a 3s interval If we want to select a transmitter manually we can do so with the buttons LEFT and RIGHT The status of the sensor bundled with an...

Page 9: ...larm occurred the icon is displayed To view these alarms enter the menu HIST HILA where the date and time since the highest measured alarm since reseting HIST _RST is displayed for each transmitter After viewing the history it s possible to reset the counter throught HIST _RST and the icon disappears 9 Automatic adjustment of the 0 point The connected digital transmitters have an inner diagnostic ...

Page 10: ...n to return the the history menu Note In case of equipping a larger quantity of transmitters the loading of the history may take a few seconds Information menu INFO NCAL Displays the date of the next transmitter calibration LCAL Displays the date of the calibration TEMP Displays the temperature of the DEGA Tc II sensor ADDR Displays the controller address on the RS485 HOST bus EXIT Returns to a hi...

Page 11: ...nged with LEFT and RIGHT and using ENTER will confirm the selection In the final part of this whole process select either YES for saving the values into the transmitters or no for finishing the calibration without saving the values Controller testing menu TEST RELE Setting the relay output TRAN Simulation of the measured values _RST Controller restart EXIT Returns to a higher menu level The entry ...

Page 12: ...required accuracy and the occurrance of disturbing gases in the atmoshpere Also carry out a functional control 1 x every three months checking the function of the entire detection system using a test gas which does not exceed the range of the sensor We recommend using gas intended for laboratory use For the functional control do not use means for testing fire alarm detectors Perform calibration on...

Page 13: ... error contact the manufacturer X SEN MISM The set sensor ID does not match with the connected sensor Checking the configuration of the sensor required X ELFAILED EL sensor test error Sensor error only informative subsides by itself X X HEATING Transmitter is in preheating mode Wait a few minutes the transmitter will automatically enter measurement mode X EE25 ERR Error reading the internal FLASH ...

Page 14: ...ct shall be replaced 616 paragraph 4 of the Commercial Code 6 The buyer who exercises the right of warranty repair is not entitled to the return of the parts that have been replaced 7 The warranty period can be extended for up to 48 months and its validity can be extended beyond the standard length on the basis of the conclusion of an individual warranty contract Further information may be obtaine...

Reviews: