background image

 

Transmitter functions

 

The detector's motherboard is equipped by status LEDs, which help in detecting problems during the installation. 
 

LED „POW“ shines at correct power

 

LED 

ALARM

“ 

shines when the alarm level is crossed 

LED 

„ERR

OR

“ 

shines in case of malfunction or an unstandard situation 

1.

 

Turning on the transmitter 

Po  After  turning  on  the  power  the  LED  "POW"  starts  shining  and  the  LED  "ERROR"  starts  flashing,  indicating  a  forming 
sequence  of  the  sensor  and  automatic  testing  procedures,  which  can  take  up  to  180s  depending  on  the  sensor  used.  The 
output of the current loop is 1mA. During this sequence, testing of internal electronics and stabilization of the sensor in order 
to eliminate false alarms after turning on, is taking place. After completion of the formation, a 4mA current begins to flow on 
the output of the current loop and the transmitter starts working according to it's settings. 

2.

 

Gas detection 

The transmitter continuously measures the detected gas concentration in the atmoshpere and converts it's current value into 
a 4-20 mA signal or transmits it's value to the evaluation unit via DEGA protocol. 

3.

 

Malfunction 

If a malfunction of the electronics or the sensor is found during operation, the transmitter will continue transmitting via 
current loop 0,5mA. 

On the PCB this condition is indicated by the yellow „ERR

OR

“ LED.

 

4.

 

Monitoring the calibration periods 

The transmitter continuously checks the calibration validity of the connected sensor. 
 
After 12 months since the last calibration (Max. calibration interval) the LED "ERROR" starts  flashing. The  connected sensor 
must be calibrated immediately. The transmitter will transmit the information about the ending calibration via current loop. 
The  transmission  will  be  the  following:  10s  transmitting  a  4-20mA  signal  informing  about  the  actual  gas  concentration 
following a 1 second interval of 2mA current. 

Operation, maintenance, inspection and service of the transmitter

  

1.

 

Usage limits 

To maintain proper operation of the transmitter it is neccesery to respect the fact, that step changes of humidity, 
condensation or rapid changes of pressure can cause incorrect indication of the measured value. Each sensing technology is 
suited for different methods of application, which is described below. All sensors are characterized by a smaller or larger cross-
sensitivity to other gases than those which are set. Therefore before processing project documentation we recommend to 
have the air in the deployment area of the detection system analyzed. 
 

 

a) 

catalytic sensors:

 Trace amount of vapors of silicon compounds and sulfur compounds cause a permanent loss of sensitivity, 

which requires recalibration or replacement of the sensor. Longterm crossing of the measuring range causes a decrease in 
sensitivity. In case of an atmoshpere having an oxygen content of less than 17%, there will be an underestimaton of the 
measured value. In case of an atmoshpere having an oxygen content of more than 25%, there will be an overestimation of the 
measured value. 
 
b) 

electrochemical sensors:

 Constant exposure to toxic gases or short-term exposure to gases, which greatly exceed the 

maximum range of the sensor, can damage the electrochemical sensor, which requires recalibration or replacement. High 
temperature along with low relative humidity have a negative effect on the sensor's lifetime. In case of an atmoshpere having 
an oxygen content of less than 1% for longer than 1 hour, there will be an underestimation of the measured value. 
 
c) 

infrared sensors:

 Vapor acids and alkalis can etch the optical system and distort the measurements. A check or a calibration 

may be neccesery. 
 
d) 

semiconductor sensors: 

Short-term exposure to gases or vapors of organic solvents, which greatly exceed the maximum 

range of the sensor, may damage the sensor and a recalibration or replacement may be required. In case of an atmoshpere 
having na oxygen content of less than 18%, there will be an underestimation of the measured value. 

Summary of Contents for NB*-*CL III Series

Page 1: ...eof in any form without the prior permission of DEGA CZ s r o is prohibited DEGA CZ s r o reserves the right to alter the specifications of the hardware and software described in this manual at any time and without prior notice DEGA CZ s r o bears no liable for any damage resulting from use of this device ...

Page 2: ...10 5 Transmitters with a PID sensor NSx PL III PID 11 Attachments 11 1 Chart for setting the transmitter adress 11 2 Signalization transmitted by the current loop 4 20mA 12 3 Content of package 12 General warranty terms and conditions 12 For your safety Assamble the transmitter with the sensor facing downwards To maintain IP protection the transmitter must be assambled with the sensor module facin...

Page 3: ...mitter automatically checks it s calibration period the period of validity of it s calibration After 12 months since the last calibration Max calibration period the transmitter will transmit this fact to the host system The transmitter must be calibrated immediately at a certified service center with a valid certificate of competance or the manufacturer See section Monitoring the calibration perid...

Page 4: ...bustion reaction The reaction is supported by a suitable temperature and the pressence of a catalyst These sensors can be used to detect a broad range of flammable gases The sensors are characterized by fast response a long lifetime and high stability A minimum of 10 of Oxygen in the air is required for it s proper function DEGA NBx IL III with an infrared sensor NDIR Top quality scanning method T...

Page 5: ...dy of the transmitter the removable sensor and bushings Transmitter assembly procedure is as follows a Disassemble the transmitter with the four hexagon socket screws 3mm b Use a screwdriver to break out holes for the bushings c Mount the transmitter on a flat surface with four 6mm fasteners in height above the floor with the gas entrance facing downwards as specified by the detected substance d D...

Page 6: ... of cable depends on the fire report and the protocol for determining external influences 2 Setting the RS485 adress of the transmitter Each transmitter must have a unique adress within the entire bus otherwise there will be communication collisions and malfunctions The transmitter adress can either be set internally using the DegaConfig program or using the DIP switch on the PCB If the position 6...

Page 7: ...tion maintenance inspection and service of the transmitter 1 Usage limits To maintain proper operation of the transmitter it is neccesery to respect the fact that step changes of humidity condensation or rapid changes of pressure can cause incorrect indication of the measured value Each sensing technology is suited for different methods of application which is described below All sensors are chara...

Page 8: ...on the purity of the environment required accuracy and the occurrance of disturbing gases in the atmoshpere Also carry out a functional control 1 x every three months checking the function of the entire detection system using a test gas which does not exceed the range of the sensor We recommend using gas intended for laboratory use For the functional control do not use means for testing fire alarm...

Page 9: ...3 obj 2 st 24 vol 3 st 26 obj 4 st 27 vol Meets RoHS 0 1 Air DEGA NBO3 EL III Ozone O3 0 5 ppm 0 0 2ppm 1 st 0 1 ppm 2 st 0 13 ppm 3 st 0 17 ppm 4 st 0 2 ppm ALARM PEL 0 05 ppm 8h 0 01ppm Ozone 0 3 ppm DEGA NBHCL EL III Hydrogen chloride HCl 0 20 ppm 0 10ppm 1 st 4 9 ppm 2 st 6 ppm 3 st 8 ppm 4 st 9 3 ppm ALARM PEL 5 43 ppm 8h 0 1 ppm Hydrogen chloride 10 ppm DEGA NBH2S EL III Hydrogen sulfide H2S...

Page 10: ...5 LEL 2 st 10 LEL 3 st 15 LEL 4 st 20 LEL 0 1 Ethanol 20 LEL DEGA NBC2H4 IL II Ethylene 0 100 LEL 0 20 LEL 1 st 5 LEL 2 st 10 LEL 3 st 15 LEL 4 st 20 LEL 0 1 Ethylene 20 LEL DEGA NBC2H4O IL II Ethylen oxide 0 100 LEL 0 20 LEL 1 st 5 LEL 2 st 10 LEL 3 st 15 LEL 4 st 20 LEL 0 1 Ethylen oxide 20 LEL DEGA NBC6H14 IL II Hexane 0 100 LEL 0 20 LEL 1 st 5 LEL 2 st 10 LEL 3 st 15 LEL 4 st 20 LEL 0 1 Hexane...

Page 11: ...Ethanol 0 5000 ppm 0 1536 ppm 1 st 384 ppm 2 st 768 ppm 3 st 1152 ppm 4 st 1536 ppm 1 ppm Isobutylen 300ppm NBC3H8O PL III PID Isopropylalkohol 0 5000 ppm 0 400 ppm 1 st 100 ppm 2 st 200 ppm 3 st 300 ppm 4 st 400 ppm 1 ppm Isobutylen 300ppm NBC4H8O PL III PID Methylethylketon 0 5000 ppm 0 306 ppm 1 st 77 ppm 2 st 153 ppm 3 st 231 ppm 4 st 306 ppm 1 ppm Isobutylen 300ppm NBC8H8 PL III PID Styren 0 ...

Page 12: ...thorised person in possession of a valid certificate from the manufacturer 5 Claims regarding a product defect that can be dealt with reasonably quickly and without additional consequences will be resolved by remedying the defect repair or by replacement of the product part because in such a case it is a contradiction of the standard norms that the entire product shall be replaced 616 paragraph 4 ...

Page 13: ... the claims procedure go to www dega cz Manufacturer DEGA CZ s r o Malešická 2850 22c 130 00 Praha 3 Czech republic Tax ID CZ 279 029 43 IČO 279 02 943 Telephone 420 774 447 660 E mail info dega cz Web www dega cz 2016 DEGA CZ s r o User Manual ver 03DEGANBx yLIII1212018 ...

Reviews: