DEGA NBC2H4-EL III 

Ethylene oxide 

(C

2

H

4

O) 

 10 ppm 

0-1,5 ppm 

1. st. 0,5 ppm, 2. st. 0,8 ppm 
3. st. 1,2 ppm, 4. st. 1,5 ppm 

0,1 ppm 

Ethylene oxide 

 2 ppm 

DEGA NBC2H4O-EL III 

Hydrogen 

(H

2

0 - 1000 ppm 

0-400 ppm 

1. st. 100 ppm, 2. st. 200 ppm 
3. st. 300 ppm, 4. st. 400 ppm 

1ppm 

Hydrogen 

 400 ppm 

DEGA NBH-EL III 

Hydrogen cyanide 

(HCN) 

0 - 100 ppm 

0-8,3 ppm 

1. st. 2,5 ppm, 2. st. 5,0 ppm 
3. st. 6,2 ppm, 4. st. 8,3 ppm 

1 ppm 

Hydrogen cyanice 

10 ppm 

DEGA NBH-EL II 

Phosphine 

  (PH3) 

0 - 5 ppm 

 

0-0,2 ppm 

1. st. 0,06 ppm, 2. st. 0,1 ppm 
3. st. 0,15 ppm, 4. st. 0,2 ppm 

0,1 ppm 

Phosphine 

 0,3 ppm 

DEGA NBHCN-EL II 

Silane (SiH

4

0 - 50 ppm 

0-5 ppm 

1. st. 2 ppm, 2. st. 3 ppm 
3. st. 4 ppm, 4. st. 5 ppm 

0,1 ppm 

Silane 6 ppm 

DEGA NBPH3-EL II 

Chlorine dioxide 

(ClO

2

0-1 ppm 

0-0,2 ppm 

1. st. 0,06 ppm, 2. st. 0,1 ppm 
3. st. 0,15 ppm, 4. st. 0,2 ppm 

0,01 ppm 

Chlorine dioxide 

0,3 ppm 

DEGA NBSIH4-EL II 

Other chemical 

substances 

according to 

customer 

requirements 

Depending on the 

type of sensor 

 

According to chemical substance 

According 

to 

chemical 

substance 

According to 

chemical 

substance 

 

3.

 

Transmitters with an infrared sensor NBx-IL III 

 

Transmitter type 

Detected gas 

Measurement 

range 

Measurment of 

current loop 

 (4-20mA) 

Standard alarm setting 

Resolution 

Calibration gas 

DEGA NBCO2-IL III 

Carbon dioxide 

(CO2) 

0-5 % vol. 

0-2,5 % vol. 

1. st. 0,5%, 2. st. 1% 
3. st. 2%, 4. st. 2,5% 

0,1 % 

Carbon dioxide 

2,5% 

DEGA NBM-IL III 

Methane (CH4) 

/ Natural gas 

/Coal gas / CNG 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Methane 0,88% 

DEGA NBP-IL III 

Butane / LPG 
/ Propane-Butane  

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Butane 0,32 % 

DEGA NBB-IL III 

Gasoline vapors 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Hexane 0,18 % 

DEGA NBC2H6-IL II 

Ethane 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Etane 20% LEL 

DEGA NBC2H5OH-IL II 

Ethanol 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Ethanol 20% LEL 

DEGA NBC2H4-IL II 

Ethylene 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Ethylene 

  20% LEL 

DEGA NBC2H4O-IL II 

Ethylen oxide 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Ethylen oxide 

20% LEL 

DEGA NBC6H14-IL II 

Hexane 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Hexane  20% LEL 

DEGA NBN2O-IL II 

Nitrous oxide 

0-1% vol 

0-0,5% vol 

1. st. 0,125% vol, 2. st. 0,25% vol 

3. st. 0,375% vol, 4. st. 0,5% vol 

0,01 % 

Nitrous oxide  

0,5% vol 

DEGA NBC5H12-IL II 

Pentane 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Pentane  20% LEL 

DEGA NBC3H6-IL II 

Propene 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Propene  20% LEL 

DEGA NBC2H6-IL II 

Ethane 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Ethane  20% LEL 

DEGA NBL-IL II 

Other flamable 

and combustible 

gases and vapors 

according to the 

selectivity of the 

sensor 

0

100% LEL 

0-20% LEL 

1. st. 5% LEL, 2. st. 10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1% LEL 

According to the 
selectivity of the 

sensor 

4.

 

Transmitters with a semiconductor sensor NBx-SL III 

 

Transmitter type 

Detected gas 

Measurement 

range 

Measurment of 

current loop 

 (4-20mA) 

Standard alarm setting 

Resolution 

Calibration gas 

DEGA NBC-SL III 

Carbon monoxide 

(CO) 

0- 1.000 ppm 

0-130 ppm 

1. st. 26 ppm, 2. st. 45 ppm 
3. st. 68 ppm, 4. st. 87 ppm 

1 ppm 

Carbon monoxide 

130 ppm 

DEGA NBM-SL III 

Methane /CNG 

/ Natural gas 

0

100 % LEL 

0-20 % LEL 

1. st. 5% LEL, 2. st.10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Methane 0,88 % 

DEGA NBP-SL III 

Butane / LPG 

/ Propane-Butane 

0

100 % LEL 

0-20 % LEL 

1. st. 5% LEL, 2. st.10% LEL 

3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Butane 0,32 % 

DEGA NBA-SL III 

Ammonia 

(NH

3

0-1.000 ppm 

0-300 ppm 

1. st. 75 ppm, 2. st.150 ppm 

3. st. 225 ppm, 4. st. 300ppm 

1 ppm 

Ammonia 

300ppm 

DEGA NBB-SL III 

Gasoline and 
diesel vapors 

0

100% LEL 

0-20 % LEL 

1. st. 5% LEL, 2. st. 10% LEL 

 3. st. 15% LEL, 4. st. 20% LEL 

0,1 % 

Hexane 0,18% 

DEGA NBF-SL III 

Freon R134a 

0

600 ppm 

0-600 ppm 

1. st. 150ppm, 2. st.300 ppm 

3. st. 450 ppm, 4. st. 600ppm 

1 ppm 

 R134a 600ppm 

Summary of Contents for NB*-*CL III Series

Page 1: ...eof in any form without the prior permission of DEGA CZ s r o is prohibited DEGA CZ s r o reserves the right to alter the specifications of the hardware and software described in this manual at any time and without prior notice DEGA CZ s r o bears no liable for any damage resulting from use of this device ...

Page 2: ...10 5 Transmitters with a PID sensor NSx PL III PID 11 Attachments 11 1 Chart for setting the transmitter adress 11 2 Signalization transmitted by the current loop 4 20mA 12 3 Content of package 12 General warranty terms and conditions 12 For your safety Assamble the transmitter with the sensor facing downwards To maintain IP protection the transmitter must be assambled with the sensor module facin...

Page 3: ...mitter automatically checks it s calibration period the period of validity of it s calibration After 12 months since the last calibration Max calibration period the transmitter will transmit this fact to the host system The transmitter must be calibrated immediately at a certified service center with a valid certificate of competance or the manufacturer See section Monitoring the calibration perid...

Page 4: ...bustion reaction The reaction is supported by a suitable temperature and the pressence of a catalyst These sensors can be used to detect a broad range of flammable gases The sensors are characterized by fast response a long lifetime and high stability A minimum of 10 of Oxygen in the air is required for it s proper function DEGA NBx IL III with an infrared sensor NDIR Top quality scanning method T...

Page 5: ...dy of the transmitter the removable sensor and bushings Transmitter assembly procedure is as follows a Disassemble the transmitter with the four hexagon socket screws 3mm b Use a screwdriver to break out holes for the bushings c Mount the transmitter on a flat surface with four 6mm fasteners in height above the floor with the gas entrance facing downwards as specified by the detected substance d D...

Page 6: ... of cable depends on the fire report and the protocol for determining external influences 2 Setting the RS485 adress of the transmitter Each transmitter must have a unique adress within the entire bus otherwise there will be communication collisions and malfunctions The transmitter adress can either be set internally using the DegaConfig program or using the DIP switch on the PCB If the position 6...

Page 7: ...tion maintenance inspection and service of the transmitter 1 Usage limits To maintain proper operation of the transmitter it is neccesery to respect the fact that step changes of humidity condensation or rapid changes of pressure can cause incorrect indication of the measured value Each sensing technology is suited for different methods of application which is described below All sensors are chara...

Page 8: ...on the purity of the environment required accuracy and the occurrance of disturbing gases in the atmoshpere Also carry out a functional control 1 x every three months checking the function of the entire detection system using a test gas which does not exceed the range of the sensor We recommend using gas intended for laboratory use For the functional control do not use means for testing fire alarm...

Page 9: ...3 obj 2 st 24 vol 3 st 26 obj 4 st 27 vol Meets RoHS 0 1 Air DEGA NBO3 EL III Ozone O3 0 5 ppm 0 0 2ppm 1 st 0 1 ppm 2 st 0 13 ppm 3 st 0 17 ppm 4 st 0 2 ppm ALARM PEL 0 05 ppm 8h 0 01ppm Ozone 0 3 ppm DEGA NBHCL EL III Hydrogen chloride HCl 0 20 ppm 0 10ppm 1 st 4 9 ppm 2 st 6 ppm 3 st 8 ppm 4 st 9 3 ppm ALARM PEL 5 43 ppm 8h 0 1 ppm Hydrogen chloride 10 ppm DEGA NBH2S EL III Hydrogen sulfide H2S...

Page 10: ...5 LEL 2 st 10 LEL 3 st 15 LEL 4 st 20 LEL 0 1 Ethanol 20 LEL DEGA NBC2H4 IL II Ethylene 0 100 LEL 0 20 LEL 1 st 5 LEL 2 st 10 LEL 3 st 15 LEL 4 st 20 LEL 0 1 Ethylene 20 LEL DEGA NBC2H4O IL II Ethylen oxide 0 100 LEL 0 20 LEL 1 st 5 LEL 2 st 10 LEL 3 st 15 LEL 4 st 20 LEL 0 1 Ethylen oxide 20 LEL DEGA NBC6H14 IL II Hexane 0 100 LEL 0 20 LEL 1 st 5 LEL 2 st 10 LEL 3 st 15 LEL 4 st 20 LEL 0 1 Hexane...

Page 11: ...Ethanol 0 5000 ppm 0 1536 ppm 1 st 384 ppm 2 st 768 ppm 3 st 1152 ppm 4 st 1536 ppm 1 ppm Isobutylen 300ppm NBC3H8O PL III PID Isopropylalkohol 0 5000 ppm 0 400 ppm 1 st 100 ppm 2 st 200 ppm 3 st 300 ppm 4 st 400 ppm 1 ppm Isobutylen 300ppm NBC4H8O PL III PID Methylethylketon 0 5000 ppm 0 306 ppm 1 st 77 ppm 2 st 153 ppm 3 st 231 ppm 4 st 306 ppm 1 ppm Isobutylen 300ppm NBC8H8 PL III PID Styren 0 ...

Page 12: ...thorised person in possession of a valid certificate from the manufacturer 5 Claims regarding a product defect that can be dealt with reasonably quickly and without additional consequences will be resolved by remedying the defect repair or by replacement of the product part because in such a case it is a contradiction of the standard norms that the entire product shall be replaced 616 paragraph 4 ...

Page 13: ... the claims procedure go to www dega cz Manufacturer DEGA CZ s r o Malešická 2850 22c 130 00 Praha 3 Czech republic Tax ID CZ 279 029 43 IČO 279 02 943 Telephone 420 774 447 660 E mail info dega cz Web www dega cz 2016 DEGA CZ s r o User Manual ver 03DEGANBx yLIII1212018 ...

Reviews: