8
The input can only be calibrated when a correct input
signal is applied.
Adjustments can be made from -10.0
to +10.0°C, and 0.1 is the smallest increment that can
be used.
Click
OK
to write the change to the transmitter. The
display will show ‘Waiting’, and then ‘Input Updated’.
Click
Close
to exit the calibration screen. (It is not
necessary to program changes to the transmitter aft er
calibration.)
At the time of calibration, a date and time stamp is
recorded in the transmitter and displayed in the
Input
Zero Adjust
panel as shown.
Calibration information is also stored in a text fi le on
your computer and can be accessed by clicking
Logs
, or
by navigating to the folder:
My Documents
/
TM Setup
/
cal serialnumber.txt
If you change the input type (i.e. from RTD to T/C), the
calibration value will be cleared.
Changing the range
scaling does not clear the calibration.
See Appendix B for information on errors & other
dialogues that may appear during zero adjustment.