DSE Model 8620 AMF Controller Operators Manual
71
Test
This button places the module into its ‘Test’ mode. This allows an on load test of the
generator.
Once in Test mode the module will respond to the start
button, start the engine,
and run on load.
For further details, please see the more detailed description of ‘Test operation’
elsewhere in this document.
Transfer to mains
Operative in Manual Mode only
‘Normal’ breaker button control
•
Allows the operator to transfer the load to the mains
•
If the Generator is on load and mains is available the generator will
synchronise and parallel with the mains.
•
If the Generator & mains are in parallel, the generator power will ramp off and
open the generator breaker.
‘Alternative’ breaker button control ( Synchronises when necessary )
•
If generator is on load, transfers the load to the mains.
•
If mains is on load, opens the mains breaker
•
If generator and mains are off load, closes the mains breaker.
Transfer to generator
Operative in Manual Mode only
‘Normal’ breaker button control
•
Allows the operator to transfer the load to the generator
•
If the mains is on load and the generator is available the generator will
synchronise and parallel with the mains.
•
If the mains & generator are in parallel the generator power will ramp up and
open the mains breaker.
‘Alternative’ breaker button control ( Synchronises when necessary )
•
If mains is on load, transfers the load to the generator.
•
If generator is on load, opens the generator breaker
•
If generator and mains are off load, closes the generator breaker
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items elsewhere
in this manual
The following description details the sequences followed by a module containing the standard ‘factory
configuration’.
Remember that if you have purchased a completed generator set or control panel from your
supplier, the module’sconfiguration will probably have been changed by them to suit their particular
requirements.
Always refer to your configuration source for the exact sequences and timers observed by any
particular module in the field.