20181270 CR v8-2019Page 37
Location of fittings:
These products must be secured onto a structure made from wood or reinforced concrete. This structure
must be firm and sturdy enough to withstand a weight of over 200 kg and able to withstand vibrations
over long periods.
The cassette must be suspended as shown in the diagram below:
Adjust the relative position of the
hook
Adjust the position of the suspension hooks so that the appliance is level in all directions. After
installation, use a spirit level to ensure that the indoor unit is positioned horizontally; if the unit is not
level this could lead to water/air leaks, etc.
Tighten the bolts and ensure that the four hooks are properly tightened using the washers and nuts to
secure the indoor unit to the ceiling.
Once the appliance has been installed, ensure that it is securely fixed for safety reasons and that it does
not move from side to side.
Ensure that the centre of the indoor unit is aligned with the centre of the opening in the ceiling.
Condensate discharge:
The condensate lift pump is built into UCARE indoor units
1. The drain pipe must be corrected insulated to prevent the formation of condensation. It must be
installed on a downward slope (1/100-150).
Product check
Protection
Suspension
hook with
nut
Integrate
d hook
Suspension hook
Nut
Washers
Spring washer