0.12 Optional Panel - Burner wiring with BMS

Application wiring: Example burner wiring 2 stage (L-H-L)
operation, main power provided to panel then to burner.
ALL WIRING BETWEEN BURNER AND PANEL AS SHOWN
INSTALLED BY OTHERS
1. 
Main power disconnect fuse 15A max

2. Service switch (located near boiler in an accessible location)

3. Low water cutoff control (2 possible wiring connections)

4. Vent safety device installed on venting

5. Optional instead of vent safety device a jumper can be installed

between 6-7 if the burner is equipped with a high gas or over
pressure switch (manual reset) power disconnect fuse 15A max

Wiring does not show burner motor connections or additional bur-
ner wiring required. 2 stage operation requires a 2 stage firing relay 
as shown in the diagram, this firing relay is sold as an option and is 
not provided with the standard panel, unless specifically ordered.

MAN/AUTO/STB Switch 

MAN = Position for the basic panel operation.
STB = Testing safety (fixed Hi-limit)
AUTO = Position remote BMS operation

BMS or Digital Control Sensor Wiring

4

5

6

7

10

11

8

13

14

12

16

15

19

17

21

20

25

28

29

27

31

30

33

34

32

36

35

38

37

Thermostat 

(Optional)

TS

2

3

1

(1) 

AUTO

(1a) STB

(1b)MAN

T

CH1

TCH2

ZSTB

ZG

DJ10A

In

te

rnal

 W

ir

in

g

 –

B

y F

actor

y Do

 no

t Mod

ify

D

e

 Di

etri

ch Co

ntro

l Panel

S2NA 

(ME50) =

 G

T

120-220

A Seri

es 

bo

il

ers

S3NA (MD5) = 

G

T

330

-430-530A Serie

s

(2

AUT

O

(2a) STB

(2b) 

MAN

9

22

23

24

26

18

ZP

(2a)
 

AU
TO

(1a)
 

AU
TO

(2b)
 

MA

N

(1b)
 

MA

N

(2) OFF

(1) OFF

N

L

AC Supply

120/60/1 – 15A Max

3

2

1

120/60/1

Main Power Supply

CS – Safety 

Contact 120v

Burner Connections

Heating 

Pump 

DHW

Pump 

120/24v

Transformer 

BMS or Digital Control Wiring

1

st

Stage

2

nd

stage

Gnd

N

Only used with Optional 

BMS & Digital Control

L

1

2

3

4

4

X

= Burner terminals - not all 
terminal designations shown

3*

BMS (Remote)

x

x

L

N

N

L

x

x

x

x

x

x

All contact must be (dry)

Operator (Limit)

1 stage control

Operator (Limit)

2 stage control

Heating 

Pump Control

DHW Pump 

Control

Open terminals

N

GND

X X

k1

X X

Limit circuit 

(Operator)

2

nd

stage 

Limit circuit 

(Operator)

Panel Internal Wiring Legend

symbol

Description

ZG main power switch

Earth Ground

DJ 10A Fuse breaker

TS – Safety limit (SPDT) manual reset 

Panel wire terminals

ZSTB switch Man/Auto/STB 

TCH1 – 1

st

stage or 

limit control

TCH2 – Aux Limit or 2

nd

stage Limit (optional usage)

ZP – Aux (pump) switch AUTO/OFF/MAN

1

Common connection

All wiring min 18awg. (16 strd) type 
CSA TEW or UL1015 (rated for at least 300v - 90°C) 
All panels to be earth leakage test (Di-electric) and function tested
All components North American approved (see material listing)

Factory wiring Line 

(Hot or L1)

Factory wiring Neutral 

(N or L2)

Blocked vent safety interlock 

(jumper if burner equipped)

ZSTB
switch

ZP

AUTO

MAN

STB

OFF

MAN

AUTO

ATTENTION – WARNING

FAILURE TO FOLLOWING THIS WIRING DIAGRAM MAY RESULT IN PROPERTY 
DAMAGE OR PERSONAL INJURY INCLUDING DEATH.

Wiring must be in strict compliance with CSA C22.2 and NEC/NFPA 70.
All wiring shown supplied and wired by others.
Panel 2

nd

Stage output used 2-stage limit control or as a auxiliary limit works with the 

1

st

limit.

This equipment must be earth bonded or grounded.
All wiring (field or replacement) must be min 18AWG type CSA TEW/ UL 1015 rated 
300v - 90°C minimum.
All wiring and panels must be shielded from spray or ingestion of water.
Any portion of the control which has been subject to spray or ingestion of water, the 
entire control must be replaced.
It is the responsibility of the installer/owner to verify the controls are functioning 
correctly and are adjusted correctly.
Suitable wire protection and strain relief’s are required (upstream & downstream) of 
the control panel.
Line voltage wiring and low voltage sensor wiring must use separate wire conduits.
LABEL ALL WIRES PRIOR TO DISCONNECTING THEM FOR SERVICE.

Summary of Contents for ME50

Page 1: ...symbols or important items The operating manual is part of the documentation along with the boiler The installer is required to explain the heating system and boiler operating instructions to the owner Notice Please read this manual and retain for future reference Improper installation adjustment alteration service or maintenance can cause injury loss of life or property damage Refer to this manua...

Page 2: ...person or company There are no owner serviceable parts on this control the usage of Non OEM parts void any product warranty and approvals The manufacturer is not responsible nor held liable for any improper use or failure to maintain this control is good operating condition Always Observe the power polarity This control requires to be earth grounded bonded If the control must be protected from wat...

Page 3: ... Boiler Modification and spare parts This boiler use specific original manufactured parts the boiler must not be modified or use non OEM parts without the written approval from DDR Americas Inc De Dietrich Boilers Installation servicing maintenance of this boiler shall be completed by a licenced and trained individual experinced in hot water boiler heating and gas oil combustion The installation m...

Page 4: ...TB safety test button testing of fixed hi limit 9 Illuminated main On Off switch 10 AUTO O MANU pump control not part of the safety or operating limits AUTO digital control pump operation O pump off MAN basic panel pump control pump operates continously 0 4 Technical Info Power supply 120VAC 10 single phase with neutral and ground earth Maximum 10A operation fuse breaker protected Safety Hi Limit ...

Page 5: ...ll make electrical connections All wiring must comply with the latest national and local electrical codes NEC NFPA70 CSA 22 2 Main fuse disconnect must be provided 15A max Suitable strain relief and wire protection must be provided All wiring UL CSA approved type suitable for the installation and must be at least 18awg 0 75mm2 rated for 300v 90 C min The equipment must be earth grounded bonded No ...

Page 6: ... X X N L Operator Limit Circuit Gnd 1 2 3 4 4 X Burner terminals not all terminal designations shown 3 5 Open terminals Panel Internal Wiring Legend symbol Description ZG main power switch Earth Ground DJ 10A Fuse breaker TS Safety limit SPDT manual reset Panel wire terminals ZSTB switch Man Auto STB TCH1 1st stage or limit control TCH2 Aux Limit or 2nd stage Limit optional usage ZP Aux pump switc...

Page 7: ...ital Control Wiring 1st Stage 2nd stage Gnd N Only used with Optional BMS Digital Control N L Gnd 1 2 3 4 4 X Burner terminals not all terminal designations shown 5 3 7 Open terminals ATTENTION WARNING FAILURE TO FOLLOWING THIS WIRING DIAGRAM MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY INCLUDING DEATH Wiring must be in strict compliance with CSA C22 2 and NEC NFPA 70 All wiring shown supplied...

Page 8: ... This control are not pro vided and are by others MAN AUTO STB Switch Must be in the MAN position for the basic panel operation STB Testing safety fixed Hi limit AUTO Not used no function ATTENTION WARNING FAILURE TO FOLLOWING THIS WIRING DIAGRAM MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY INCLUDING DEATH Wiring must be in strict compliance with CSA C22 2 and NEC NFPA 70 All wiring shown supp...

Page 9: ...rol BURNER CONTROL POWER N L Gnd 1 2 3 4 4 X Burner terminals not all terminal designations shown 3 X X k1 X X Limit Circuit Operator 2nd stage Limit Circuit Operator Open terminals ATTENTION WARNING FAILURE TO FOLLOWING THIS WIRING DIAGRAM MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY INCLUDING DEATH Wiring must be in strict compliance with CSA C22 2 and NEC NFPA 70 All wiring shown supplied a...

Page 10: ...iring 1st Stage 2nd stage Gnd N Only used with Optional BMS Digital Control BURNER CONTROL POWER N L Gnd 1 2 3 4 4 X Burner terminals not all terminal designations shown 3 T6 T7 T8 k 1 T1 T2 Limit Circuit Operator 2nd Stage Limit Circuit 2nd stage operator Open terminals ATTENTION WARNING FAILURE TO FOLLOWING THIS WIRING DIAGRAM MAY RESULT IN PROPERTY DAMAGE OR PERSONAL INJURY INCLUDING DEATH Wiri...

Page 11: ...wn 3 BMS Remote x x L N N L x x x x x x All contact must be dry Operator Limit 1 stage control Operator Limit 2 stage control Heating Pump Control DHW Pump Control Open terminals N GND X X k1 X X Limit circuit Operator 2nd stage Limit circuit Operator Panel Internal Wiring Legend symbol Description ZG main power switch Earth Ground DJ 10A Fuse breaker TS Safety limit SPDT manual reset Panel wire t...

Page 12: ...12 GT 220A 06 01 09 XXXX XXXX R0 T T T T T T T T 0 1 0 0 1 0 0 13 Principle wirig diagram ...

Page 13: ...13 11 13 09 XXXX XXXX R0 GT 220A 0 1 55 56 57 58 58 59 60 61 ...

Page 14: ...14 GT 220A 06 01 09 XXXX XXXX R0 ...

Page 15: ...15 11 13 09 XXXX XXXX R0 GT 220A ...

Page 16: ...ario N3E 1A3 CANADA Tel 519 650 0420 Fax 519 650 1709 In USA or South America 1054 North DuPage Avenue Lombard Illinois USA 60148 Tel 630 953 2374 Fax 630 953 2376 Toll Free 1 800 943 6275 www dedietrichboilers com In the interest of customers DE DIETRICH DDR Americas are continuously endeavouring to make improvements in product quality All the specifications stated in this document are therefore ...

Reviews: