![DeDietrich GT 123 A Installation And Maintenance Manual Download Page 5](http://html.mh-extra.com/html/dedietrich/gt-123-a/gt-123-a_installation-and-maintenance-manual_2462442005.webp)
5
02/10/06 - 94863361 - 85784009D
GT 120 A - GT 1200 A
2 Technical specifications of boilers
- CSA - MBH Output based on Thermal Efficiency Test According to
ANSI Z21.13a/CSA 4.9a-2005
- [NET] MBH Output Factor 1.15, Allowance for Piping and Pickup
Losses
- Chamber Resistance Based on Neutral Chimney-Vent Pressure
- Gas Vent Category Based on Several Factors [CO2 content, Vent
Pressure & Net-Flue Gas Temp]
- Approved for Direct-Vent, Use Only Approved Venting as Listed
- Natural Draft Applications, Approved for Type L vent [Gas-Oil] or
Type B Vent [Gas Only]
- Conversion Btu to kW = 3,412 Btu per kW
- All Models are Design Certified & Eligible to Bear Approval Marking
as Shown.
- All Models Certified to Fire; # 2 oil, Natural & Propane Gases.
Consult factory for Available Burners.
- All Models Comply and Certified in Accordance to the latest
Canadian & US standards
- To Obtain Current IBR Ratings, consult their publications and
website.
Item
Unit
GT 123 A
GT 124 A
GT 125 A
GT 126 A
Firing Sequence
Gas-Oil - On-Off - Single Stage Only
[CSA] - Gas Input
MBH
94
115
144
166
kW
27.5
33.7
42.2
48.65
[CSA] - # 2 Fuel Oil Input
US GPH
0.65
0.80
1.00
1.15
[CSA] - Output [Gas-Oil]
MBH
78
96
120
138
kW
22.9
28.1
35.2
40.4
[NET] - Output [Gas-Oil]
MBH
68
83
104
120
[CSA] - AFUE Effy.
%
Gas 85% & Oil 87%
Cast Iron Sections
#
3
4
5
6
+HDWLQJVXUIDFHDUHD6TIW
Water capacity
US Gal
5
6.5
7.9
9.4
Liter
19
24.5
30
35.5
Water resistance
[
∆
t = °F]
18° F
Ft. H
2
O
0.13
0.20
0.30
0.42
27° F
Ft. H
2
O
0.06
0.09
0.14
0.19
36° F
Ft. H
2
O
0.03
0.05
0.08
0.11
Combustion chamber
Dimensions
Diameter
[Equivalent]
Inch
9.45
mm
240
Depth
Inch
12.13
17.13
22.13
27.13
mm
308
435
562
689
Volume
ft
3
0.57
0.74
0.92
1.09
m
3
16.0
21.0
26.0
31.0
MAWP [Water]
PSI
ASME IV Rating Class 30 - (60 PSI) [See Canadian Provincial CRN
approvals]
Min. Safety Relief Capacity
MBH
78
96
120
138 M
S2NA
Pan
el
Electrical Connection
V/P/H
120/1/60
Maximum Temperature [Water]
°F
230
°C
110
Operating Water Temperature Range
°F
104 - 212
°C
40 - 100
Chamber Resistance
Inch w.c.
0.06
0.09
0.09
0.09
mbar
0.15
0.22
0.22
0.22
Gas-Vent Category
#
I, II - III or IV
Boiler Vent Connection
Inch
5
5
5
6
Weight [Dry]
lb
302
357
412
470
kg
137
162
187
213
Summary of Contents for GT 123 A