Parameters
Description
Factory setting
Customer setting
SUM/WIN
Outside temperature above which the heating will be shut
down:
OFF : The heating is never shut down automatically.
Can be set from 15 to 30°C:
The heating pumps are shut down.
The heat pump only starts up for domestic hot water or
cooling needs, if the function is enabled.
The
symbol is displayed.
The symbol is displayed if the cooling function is ena
bled,
22°C
CALIBR.OUT
Outside sensor calibration
Is used to correct the outside temperature information.
Outside tempera
ture
OFFSET ROOM A
Room temperature offset on circuit A.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Can be set from -5 to +5°C.
0
OFFSET ROOM B
Room temperature offset on circuit B.
Is used to set a room temperature offset.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Can be set from -5 to +5°C.
0
OFFSET ROOM C
Room temperature offset on circuit C.
Is used to set a room temperature offset.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Can be set from -5 to +5°C.
0
PERMUT
Used to establish the pilot heat pump:
AUTO : the pilot heat pump automatically switches every 7
days
Can be set from 1 to 10: number of the heat pump chosen
as the pilot heat pump
AUTO
CALIBR.ROOM A
Calibration of the room temperature sensor on circuit A.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Room tempera
ture on circuit A
CALIBR.ROOM B
Calibration of the room temperature sensor on circuit B.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Room tempera
ture on circuit B
CALIBR.ROOM C
Calibration of the room temperature sensor on circuit C.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
Room tempera
ture on circuit C
ANTIFR.ROOM A
Room temperature at which frost protection on circuit A is ac
tivated.
Can be set from 0.5 to 20°C.
6°C
ANTIFR.ROOM B
Room temperature at which frost protection on circuit B is ac
tivated.
Can be set from 0.5 to 20°C.
6°C
ANTIFR.ROOM C
Room temperature at which frost protection on circuit C is
activated.
Can be set from 0.5 to 20°C.
6°C
6 Settings
7636860 - v04 - 18012017