background image

 

 

RANGE 
The standard range comprises 22 standard models, 
in 4 categories - floor standing, ducted floor 
standing, wall mounted and ceiling mounted. Refer 
to Diagram 2 on page 2 for model identification. 
All models are available in seven sizes (figure 
numbers), with the nominal output indicated by the 
figure number. 

 

Size 

Nominal output 

(kW) 

Casing width 

(mm) 

Fig 03 

2.6 

695 

Fig 04 

4.7 

895 

Fig 06 

6.0 

895 

Fig 08 

8.2 

1195 

Fig 10 

9.4 

1195 

Fig 12 

11.4 

1495 

Fig 15 

12.7 

1495 

Table 1: 

Nominal outputs and sizes 

 
 

CONTROLS 

Fan motors 

Conventional synchronous AC motors or energy 
efficient EC motors can be provided. EC motors are 
available as one of two options:- 
ECS - speed control by an external 2-10VDC signal 
ECM - speed control by fitted speed interface  

 

Air thermostats 

Air  thermostats  can  be  provided  to  automatically 
switch  the  heater  on/off  and  to  change  the  fan 
speed/heat  output,  in  response  to  a  fall  or  rise    in 
ambient air temperature. Thermostats can be fitted or 
remote as follows :- 
 

Fitted air thermostats - Models 13, 15, 17, 20, 21, 23 

and 25 only. 

Capillary  thermostats,  or  room  thermostats  with  an 
accelerator heater, can be fitted for on/off and speed 
change. 
 

 

Diagram 3:  Fitted on/off & high/low thermostats 
 

Remote thermostats - All models 

Standard or tamper resistant room thermostats with 
an accelerator heater, can be provided for on/off and 
speed change. 
 

Low temperature cut-out (LTC) thermostat

 

A low temperature cut-out thermostat may be  
provided to operate the heater when hot water is 
supplied to the coil. This will automatically stop the 
heater at the end of a normal operating period e.g. 
when the boiler plant shuts down:- 

Type 1 (fixed)  

 

make circuit at 50°C±3K 

 

 

 

 

break circuit 38°C±3K 

Type 2 (adjustable) 

range 30 - 90°C 

 

Switches 

Fitted switches (external, or internal) or remote 
switches (flush or surface wall mounting) can be 
provided to switch the heater on/off, change fan 
speed and/or override any thermostats.  
 

 

Diagram 4:  Fitted man/off/auto & high/low switches 
 
The man/off/auto switch allows the fans to circulate 
room air when the boiler plant is shutdown during the 
summer. 
 
A FAI/recirc switch can also be provided to open or 
close fresh air inlet (FAI) dampers (models 19, 22, 
53 and 88 with optional motorised damper). 

 

Switch types are: 

 

on/off 

 

high/off/low 

 

manual/off/auto 

 

manual/off/auto and high/low 

 

FAI/recirc 

 

FAI/recirculation and high/off/low 

 

FAI/recirculation and manual/off/auto 

 

FAI/recirculation, manual/off/auto and  

 

 

high/low 

 

Special controls 

If specified, the heater may incorporate special 
controls such as relays, thermal controls etc. 
These will be shown on the wiring diagram supplied 
with each heater. 

Summary of Contents for AM Series

Page 1: ...ION The fan convector serial number model description figure number size are displayed on a label found on the inside of the heater access panel If specified a stencil reference may also be marked on...

Page 2: ...2 Diagram 2 Range of standard models and accessories...

Page 3: ...stats All models Standard or tamper resistant room thermostats with an accelerator heater can be provided for on off and speed change Low temperature cut out LTC thermostat A low temperature cut out t...

Page 4: ...e structure to which heaters are to be fixed must be fit for purpose and capable of accepting plugs and screws anchor bolts or drop rods Floor models require a level base Floor and wall models require...

Page 5: ...onnections on page 6 7 Wire up as detailed in Electrical Connections and Controls on page 7 8 If supplied fit the adjustable type 2 low temperature cut out thermostat to the LTHW flow pipe 9 After fil...

Page 6: ...22mm plain copper tails Local isolating and regulating valves are recommended Observe the correct flow and return positions to ensure the rated heat output see Diagram 7 Fill the system and check for...

Page 7: ...und COMMISSIONING General 1 Purge air from the coil using the manual or automatic air vent or through the mains above the coil if applicable Balance the water flow rate through the system to accepted...

Page 8: ...re safe low voltage of 10VDC or less Diagram 9 Fan speed interface with 3 speeds ECM fan motor option only Size Low speed Medium speed High speed Fan voltage VDC Airflow l s Running current A SFP W l...

Page 9: ...9 Diagram 12 Typical installation detail for Models 15 and 41...

Page 10: ...10 Diagram 13 Typical installation detail for model 17...

Page 11: ...11 Diagram 14 Typical installation detail for models 19 22 53 and 88...

Page 12: ...12 Diagram 15 Typical installation detail for model 21...

Page 13: ...13 Diagram 16 Typical installation detail for models 23 and 92...

Page 14: ...14 Diagram 17 Fixing detail for loose grille and fixing frame Diagram 18 Fixing detail for plinth...

Page 15: ...15 Diagram 19 Fixing detail for suspension brackets wall and ceiling mounted units...

Page 16: ...rmal air flow All accessible surfaces can be wiped with a dry cloth Maintenance 1 Coil Purge any air from the coil using the manual air vent using a suitable key or by turning the knurled thumbwheel o...