background image

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pumps

428 01 1703 01

11

Specifications subject to change without notice.

Forced Defrost

On a system with non

communicating (non-Observer)

control, forced defrost can be initiated by manually shorting

the 2-pin header labeled FORCED DEFROST (see Fig 14)

on the control board for 5 seconds then releasing.

If coil temperature is at defrost temperature of 32

°

F

(0

°

C), and outdoor air temperature is below 50

°

F

(10

°

C), a full defrost sequence will occur.

If coil temperature or outdoor air temperature does not

meet the above requirements, an abbreviated 30

second defrost will occur.

Quiet Shift

2

Quiet Shift

2 is a field

selectable defrost mode which may

eliminate occasional noise that could be heard at the start

and finish of the defrost cycle. For installations using a

standard 2

stage thermostat, this feature must be enabled

by selecting the 3

rd

 position dip switch on the outdoor control

board. For installations using an Observer Wall Control, it

must be enabled at the Wall Control. When activated, the

following sequence of operation occurs: 

Defrost Initiation 

 the compressor is de

energized for 70

seconds. During this 70 second compressor off time, the

reversing valve will be energized. Once the 70 second

compressor off time has been reached, the compressor will

be energized then the outdoor fan will be de

energized at

which time the normal defrost cycle begins. 

Defrost Termination 

 The outdoor fan will be energized

shortly before the compressor is de

energized for 60

seconds. During the compressor 60 second off time, the

reversing valve will be de

energized. Once the 60 second

compressor off time has been completed, the compressor will

be energized at which time the system will be in normal heat

mode.

Liquid

Line Accessory

In heat pump long

line applications, a liquid

line solenoid is

required to control refrigerant migration in the heating mode.

The solenoid should be installed near the outdoor unit with

the arrow facing the outdoor unit. This is the direction of flow

control. See application manual for long

line application

details.
Accessory Liquid Solenoid with Observer Communicating

Wall Control: When using the Observer Wall Control, the

liquid-line solenoid output is provided at the Y1 connection.

Connect the solenoid as shown in the wiring label diagram.

This is a 24vac output that is energized whenever the

compressor is energized. It closes, in the compressor off

mode, to prevent refrigerant migration into the unit through

the liquid

line.

On Systems with Accessory Liquid Solenoid Using a

Non

Communicating Thermostat: The liquid solenoid is

connected to the Y1 and C terminal connections. The liquid

solenoid closes, in the compressor off mode, to prevent

refrigerant migration into the unit through the liquid

line.

TROUBLESHOOTING

If the compressor fails to operate with a cooling call, Table 4

can be used to verify if there is any damage to the

compressor windings causing system malfunction.

Table 4 

 Winding Resistance

Winding Resistance At 70

F +/

 20

F

(21.11

C +/

 11.11

C)

Winding

24

36

48

60

Start

(S

C)

1.64

1.52

1.86

1.63

Run

(R

C)

1.30

0.88

0.52

0.39

Systems Communication Failure

If communication with the Observer Communicating Wall

Control will flash the appropriate fault code. (See Table 6)

Check the wiring to the wall control, indoor and outdoor units.

Model Plug

Each control board contains a model plug. The correct model

plug must be installed for or the system to operate properly

(see Table 5).

Table 5 

 Model Plug

Model

Number

Model Plug

Number

Pin Resistance

(kOhms)

Pin 1

4

Pin 2

3

*CH624

HK70EZ041

18

91

*CH636

HK70EZ043

18

150

*CH648

HK70EZ045

18

220

*CH660

HK70EZ047

18

360

*CH924

HK70EZ010

5.1

120

*CH936

HK70EZ012

5.1

180

*CH948

HK70EZ014

5.1

270

*CH960

HK70EZ016

11

5.1

The model plug is used to identify the type and size of unit to
the control.
On new units, the model and serial numbers are input into
the board’s memory at the factory. If a model plug is lost or
missing at initial installation, the unit will operate according to
the information input at the factory and the appropriate error
code will flash temporarily.
A FAST® Parts replacement board contains no model and
serial information. If the factory control board fails, the model
plug must be transferred from the original board to the
replacement board for the unit to operate.

NOTE

The model plug takes priority over factory model

information input at the factory. If the model plug is removed
after initial power up, the unit will operate according to the last
valid model plug installed, and flash the appropriate fault code
temporarily.

Pressure Switch Protection

The outdoor unit is equipped with high and low pressure
switches.
If the control senses the opening of a high or low pressure
switch, it will respond as follows:

1.

De-energize the appropriate compressor contactor.

2.

Keep the outdoor fan operating for 15 minutes.

3.

Display the appropriate fault code (see Table 6).

4.

After a 15 minute delay, if there is still a call for cooling
and the LPS or HPS is reset, the appropriate
compressor contactor is energized.

5.

If LPS or HPS has not closed after a 15 minute delay,
the outdoor fan is turned off. If the open switch closes
anytime after the 15 minute delay, then resume
operation with a call for cooling.

Summary of Contents for CCH9

Page 1: ...hanced installation reliability or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manu...

Page 2: ...d refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube...

Page 3: ...ctions from kit for installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent damage to the unit ensure that it is located...

Page 4: ...ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 2...

Page 5: ...E HAZARD Failure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DA...

Page 6: ...d Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to fol...

Page 7: ...ment size See Observer Wall Control Installation Instructions and indoor specification sheet for available adjustments Airflow Setup with Non Communicating Furnace or Fan Coil Two stage compressor ope...

Page 8: ...age 1 Heat Stage 3 Heat Cool Stage 2 Fan 24 VAC Hot Dehumidify 24 VAC Comm Humidify RVS Heating Outdoor G O R W1 Y Y2 C Y1 W2 H O Y1 Y2 C W1 Two Stage Heat Pump Remove J2 Jumper For Heat Staging s s H...

Page 9: ...age of cooling Y1 and O are powered on and with second stage of cooling Y1 Y2 and O are on For these systems with first stage of heating Y1 is on and for second stage of heating Y1 and Y2 are on When...

Page 10: ...There is no delay between staging from low to high and from high to low capacity The compressor will change from low to high and from high to low capacity on the fly to meet the demand DEFROST This c...

Page 11: ...th Accessory Liquid Solenoid Using a Non Communicating Thermostat The liquid solenoid is connected to the Y1 and C terminal connections The liquid solenoid closes in the compressor off mode to prevent...

Page 12: ...te fault code Compressor Thermal Cutout If the control senses the compressor voltage after start up and is then absent for 10 consecutive seconds while cooling demand exists the thermal protector is o...

Page 13: ...ure If the outdoor ambient or coil thermistor should fail the control will flash the appropriate fault code see Table 6 IMPORTANT Outdoor air thermistor and coil thermistor are factory mounted in the...

Page 14: ...INSTALLATION INSTRUCTIONS R 410A Split System Heat Pumps 14 428 01 1703 01 Specifications subject to change without notice Figure 14 Two Stage Control Board...

Page 15: ...ault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check w...

Page 16: ...10A as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig...

Reviews: