background image

INSTALLATION INSTRUCTIONS

R

410A Split System Heat Pumps

10

428 01 1703 01

Specifications subject to change without notice.

the crankcase heater remains de-energized after the

compressor is turned off.

Outdoor Fan Motor Operation

The outdoor unit control energizes the outdoor fan any time

the compressor is operating.  The outdoor fan remains

energized if a pressure switch or compressor overload

should open.  Outdoor fan motor will continue to operate for

one minute after the compressor shuts off when the outdoor

ambient is greater than or equal to 100

F (37.8

C) to allow

for easier starting during next cooling cycle.
On CCH6, HCH6 and TCH6 models - The outdoor fan motor

is a PSC type. A fan relay on the control board turns the fan

off and on by opening and closing a high voltage circuit to the

motor. It does not change speeds between low and high

stage operation.
On CCH9, HCH9 and TCH9 models 

 The outdoor fan is an

ECM type. The motor control is continuously powered with

high voltage. The motor speed is determined by electrical

pulses provided by the PWM outputs on the control board.

The ECM motor RPM adjusts to outdoor conditions as

described in Table 3. The PWM output can be measured

between the PWM1 and PWM2 terminals on the circuit board

with a volt meter set to DC volts.

Table 3 

 Outdoor Fan Motor PWM

Outdoor Temp (DC volts, Tol/

 2%)

Model

Size

Low

Stage

High Stage

Low & High Stage

OAT 

 

104

F/ 40

C OAT 

 

104

F/ 40

C OAT > 104

F/ 40

C

924

8.72

9.35

11.90

936

9.06

10.23

11.90

948

9.91

11.04

11.90

960

10.83

11.70

11.90

Time Delays

The unit time delays include:

Five minute time delay to start cooling operation when
there is a call from the thermostat or Wall Control. To

bypass this feature, momentarily short and release

Forced Defrost pins or hold the “Cool To” or “Heat To”

button on the Observer Wall Control for 10 seconds.

Five minute compressor re

cycle delay on return from

a brown

out condition.

Two minute time delay to return to standby operation

from last valid communication (Observer

Communicating Wall Control only).

One minute time delay of outdoor fan at termination of

cooling mode when outdoor ambient is greater than or

equal to 100

F (37.8

C).

Fifteen second delay at termination of defrost before

the auxiliary heat (W1) is de

energized.

Twenty second delay at termination of defrost before
the outdoor fan is energized.

Seventy and sixty second compressor delays when

Quiet Shifts

2 enabled.

There is no delay between staging from low to high
and from high to low capacity. The compressor will

change from low to high and from high to low capacity

“on the fly” to meet the demand.

DEFROST

This control offers 5 possible defrost interval times: 30, 60,

90, 120 minutes, or AUTO.
Defrost intervals are selected by dip switches on the unit

control board or by the Observer Wall Control. The Observer

Wall Control selection overrides the control board dip switch

settings.
AUTO defrost adjusts the defrost interval time based on the

last defrost time as follows:

When defrost time <3 minutes, the next defrost
interval = 120 minutes.

When defrost time 3 - 5 minutes, the next defrost

interval = 90 minutes.

When defrost time 5 - 7 minutes, the next defrost
interval = 60 minutes.

When defrost time >7 minutes, the next defrost

interval = 30 minutes.

The control board accumulates compressor run time. As the

accumulated run time approaches the selected defrost

interval time, the control board monitors the coil temperature

sensor for a defrost demand. If a defrost demand exists, a

defrost cycle will be initiated at the end of the selected time

interval. A defrost demand exists when the coil temperature
is at or below 32

°

F (0

°

C) for 4 minutes during the interval.

The defrost cycle is terminated when the coil temperature
reaches 65

°

F (18.33

°

C)or 10 minutes has passed. When

OAT is > 25

°

F (-3.9

°

C), defrost will occur in low or high stage

as demanded by the thermostat or Wall Control.
If OAT is 

≤ 

25

°

F (

3.9

°

C), defrost will occur in high stage

only, regardless of thermostat or Wall Control demand, and
will terminate at 50

°

F (10

°

C) coil temperature with a

minimum of 2.5 minutes in defrost.
If the coil temperature does not reach 32

°

F (0

°

C) within the

interval, the interval timer will be reset and start over.

Upon initial power up the first defrost interval is

defaulted to 30 minutes. Remaining intervals are at

selected times.

Defrost is only allowed to occur below 50

°

F (10

°

C)

outdoor ambient temperature.

The outdoor fan output (ODF) will remain off for 20 seconds

after termination. This delay will allow time for the system to

capture the heat from the outdoor coil and reduce the “steam

cloud” effect that may occur on transition from defrost to

heating cycle.

Defrost Hold

On a non

communicating system, if the thermostat becomes

satisfied (Y1 or Y1 and Y2) before the defrost cycle is

terminated, the control will “hold” in defrost mode and finish

the defrost cycle on the next call for heat.
On models with communicating Observer Wall Control,

defrost hold is not needed because the system will complete

the defrost cycle before shutting down the system.

Summary of Contents for CCH9

Page 1: ...hanced installation reliability or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manu...

Page 2: ...d refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube...

Page 3: ...ctions from kit for installation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation To prevent damage to the unit ensure that it is located...

Page 4: ...ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 2...

Page 5: ...E HAZARD Failure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DA...

Page 6: ...d Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box WARNING ELECTRICAL SHOCK HAZARD Failure to fol...

Page 7: ...ment size See Observer Wall Control Installation Instructions and indoor specification sheet for available adjustments Airflow Setup with Non Communicating Furnace or Fan Coil Two stage compressor ope...

Page 8: ...age 1 Heat Stage 3 Heat Cool Stage 2 Fan 24 VAC Hot Dehumidify 24 VAC Comm Humidify RVS Heating Outdoor G O R W1 Y Y2 C Y1 W2 H O Y1 Y2 C W1 Two Stage Heat Pump Remove J2 Jumper For Heat Staging s s H...

Page 9: ...age of cooling Y1 and O are powered on and with second stage of cooling Y1 Y2 and O are on For these systems with first stage of heating Y1 is on and for second stage of heating Y1 and Y2 are on When...

Page 10: ...There is no delay between staging from low to high and from high to low capacity The compressor will change from low to high and from high to low capacity on the fly to meet the demand DEFROST This c...

Page 11: ...th Accessory Liquid Solenoid Using a Non Communicating Thermostat The liquid solenoid is connected to the Y1 and C terminal connections The liquid solenoid closes in the compressor off mode to prevent...

Page 12: ...te fault code Compressor Thermal Cutout If the control senses the compressor voltage after start up and is then absent for 10 consecutive seconds while cooling demand exists the thermal protector is o...

Page 13: ...ure If the outdoor ambient or coil thermistor should fail the control will flash the appropriate fault code see Table 6 IMPORTANT Outdoor air thermistor and coil thermistor are factory mounted in the...

Page 14: ...INSTALLATION INSTRUCTIONS R 410A Split System Heat Pumps 14 428 01 1703 01 Specifications subject to change without notice Figure 14 Two Stage Control Board...

Page 15: ...ault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check w...

Page 16: ...10A as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig...

Reviews: