INSTALLATION MANUAL---Installation of the outdoor unit 

The air and humidity left inside  the refrigerant circulat-
ion can cause compressor malfunction. After having co-
nnected the indoor  and outdoor units, bleed  the air and 
humidity  from  the  refrigerant  circulation  using  a va-
cuum pump. 

Refrigerant flow direction

2-way valve

(6) Open 1/4 turn

valve cap

(1) Turn

(8) Tighten

(2) Turn

3-way valve

(8) Tighten

(1) Turn

(7) Turn to fully
      open the valve

(7) Turn to fully 
      open the valve

(8) Tighten

Service 
port nut

Valve cap

(1) Unscrew and remove the caps from the  2 - way and 
      3-way valves. 
(2) Unscrew and  remove  the cap from the service port.
(3) Connect  the  vacuum pump hose to the service port.
(4) Operate the vacuum pump for  10 - 15  minutes until 
      an absolute vacuum of 10 mm Hg has been reached. 
(5) With the vacuum pump still in operation ,  close the 
      low - pressure  knob on the vacuum pump coupling. 
      Stop the vacuum pump. 
(6) Open the 2 - way valve by 1/4  turn and then close it 
      after10 seconds. Check all the joints for leaks using 
      liquid soap or an electronic leak device. 
(7) Turn the body of the 2-way and 3-way valves. 
      Disconnect the vacuum pump hose. 
(8) Replace and tighten all the caps on the valves. 

3-way valve diagram

connect to indoor unit

open position

spindle

service port cap

Connect to 
outdoor unit

Valve core

needle

INSTALLATION MANUAL--- operation test

wall

(indoor)

(outdoor)

piping

piping

gasket

insulating tape

insulating covering

Clamps

1. Wind insulating covering around the joints of the ind-
    oor unit and fix it with insulating tape.
2. Fix  the  exceeding  part  of  the  signal  cable  to  the 
    piping or to the outdoor unit.
3. Fix the piping to the wall ( after having coated it with
    insulating tape) using clamps or insert  them into pla-
    stic slots.
4. Seal the hole  in  the wall through which the piping is
    passed so that no air or water can fill.

 Do the ON/OFF and FAN  operate normally?
 Does the MODE  operate normally?
 Do the set point and TIMER function properly?
 Does each lamp light normally?
 Do the flap  for air flow direction operate normally?
 Is the condensed water drained regularly? 

 Is  there  any  abnormal  noise  or  vibration  during 

     operation?

 Could the noise ,  the air flow or the condensed water 

     drainage disturb the neighbours?

 Is there any coolant leakage?

Indoor unit test

Outdoor unit test

Note: the electronic controller allows the compressor to 
         start  only  three  minutes  after voltage has reached 
         the system.

24

BLEEDING

Indoor unit

Summary of Contents for GLAMOUR INVERTER 45 FS

Page 1: ...keep it for future reference Read This Manual to use and maintain your air conditioner properly Just a little preventative care on your part can save common problems in the chart of Troubleshooting T...

Page 2: ...S SAFETY PRECAUTIONS NAMES OF PARTS INDOOR UNIT DISPLAY OPERATING INSTRUCTIONS PROTECTION INSTALLATION MANUAL MAINTENANCE TROUBLESHOOTING REMOTE CONTROLLER 1 4 5 8 12 18 19 28 29 INDOOR UNIT CONTROL P...

Page 3: ...fire The packaging materials are recyclable and should be disposed of in the separate waste bins Take the air conditioner at the end of its useful life to a special waste collection centre for dispos...

Page 4: ...sed for any other purpose such as for drying clothes cooling food etc The packaging materials are recyclable and should be disposed of in the sparate waste bins Take the air conditioner at the end of...

Page 5: ...o not leave windows or doors open for long when the air conditioner is operating Do not direct the airflow onto plants or anim als A long direct exposition to the flow of cold air of the conditioner c...

Page 6: ...ed No Description 12 Air outlet grille Terminal block cover 13 Gas valve 14 liquid valve 15 11 Outdoor unit rating label 11 13 14 15 4 OUTDOOR UNIT 12 OUTDOOR UNIT 1 2 3 4 5 6 7 8 9 No Description 1 A...

Page 7: ...lashes in defrost circle and Anti Cold Air function FAN ONLY OPERATION indicator HEALTHY indicator Timeron Timeroff 2 3 4 6 7 5 8 18 8 10 11 14 13 12 15 16 17 Timeron Timeroff 10 11 12 13 14 15 16 17...

Page 8: ...perature in or For time in Hour 6 7 FEEL mode indicator WiFi indicator Optional COOLING indicator HEATING indicator flashes in defrost circle and Anti Cold Air function FAN ONLY OPERATION indicator HE...

Page 9: ...ture or time by 1 unit Increase the temperature or time by 1 unit To switch the conditioner on and off To select the mode of operation 7 COMPOSITE BUTTON Keep pressing the SWING button on the control...

Page 10: ...flap up down or deactivate it You will hear abeep when youpress the following buttons orselect the followingoptional functions though the actualmodel haven t thisfunction we express our apologies Opti...

Page 11: ...llowing buttons orselect the followingoptional functions though the actualmodel haven t thisfunction we express our apologies Optional Function COMFORTABLE COOLING airflow Optional Function COMFORTABL...

Page 12: ...SPLAY MILDEW 8 CH CLEAN WIND FREE GEN MODE Timer indicator Single indicator Child Lock function indicator Battery indicator Mode Auto function indicator Flashing TIMER Comfortable heating airflow indi...

Page 13: ...th er to ac tiv e Di sp la y ON O FF Lo ng pr es s EC O b ut to n Pl ea se re m ov e ba Tt er ie s to av oi d le ak ag e da m ag e w He n no t us in g fo r A lo ng tim e Note Child lock Press and toge...

Page 14: ...ill cycle as below 3 If press time interval is over 2 seconds it will be deactivate the air flow is directed alternatively from up to down In order to guarantee an even diffusion of the air in the roo...

Page 15: ...MODE button until the symbol HEAT appears on the display With the button or set a temperature higher than that of the room To optimize the function of theAir conditioner adjust the temperature 1 the...

Page 16: ...r adjust the temperature 1 the speed 2 and the direction of the air flow 3 by pressing the buttons indicated AUTO DISPLAY DISPLAY function Indoor display Switch on off the LED display on panel SLEEP S...

Page 17: ...w strong airflow To cancel this function pressing the FAN to switch other fan speed or pressing the TURBO button again Through GEN mode you can choose the current level of the unit There are three lev...

Page 18: ...er like and symbol will be on the display 4 To cancel the timer if TIMER is on Repeat step 1 step 2 then press OPTION or waiting for 5 seconds without any operation to cancel the timer A sample for th...

Page 19: ...o deactivate this function MILDEW This function enablethe air conditionerstill blow airflow about 15minutes to drythe indoor innerparts to avoid mildew when the air conditioner isoff Note MILDEW funct...

Page 20: ...ition models The unit does not operate immediately if it is turned on after being turned off or after changing the mode during operation this is a normal self protection action you need wait for about...

Page 21: ...peration regularly and reserve the necessary spaces as shown in the picture Select a place where the filter can be easily taken out minimum space to be reserved mm showing in the picture Do not instal...

Page 22: ...ing a screw 4 For the electrical connections see the circuit diagram on the right part of the unit under the front panel 5 Connect the cable wires to the screw terminals by following the numbering Use...

Page 23: ...onvenience Do not remove the cap from the pipe until connecting it to avoid dampness or dirt from entering If the pipe is bent or pulled too often it will become stiff Do not bend the pipe more than t...

Page 24: ...e wall using screw anchors which are particularly suited to the type of wall Use a larger quantity of screw anchors than normally required for the weight they have to bear to aviod vibration during op...

Page 25: ...there will also be some leakage as the flange could be damaged 3 The surest system consists in tightening the connecti on by using a fix wrench and a torque wrench Please check the torque wrench tabl...

Page 26: ...acuum pump hose 8 Replace and tighten all the caps on the valves 3 way valve diagram connect to indoor unit open position spindle service port cap Connect to outdoor unit Valve core needle INSTALLATIO...

Page 27: ...m 5m 5m 15m 15m 15m 50g m 50g m 5m 5m 5m 1 Refer to the data rating label sticked on the outdoor unit TIGHTENING TORQUE FOR PROTECTION CAPS AND FLANGE CONNECTION 25 PIPE 1 4 6 3 8 9 52 1 2 12 5 8 15 8...

Page 28: ...different Please refer to the wiring diagrams pasted on the indoor unit and outdoor unit respectively On indoor unit the wiring diagram is pasted under the front panel On outdoor unit the wiring diag...

Page 29: ...2 0 75mm 2 2 5mm AWG12 2 2 5mm AWG12 2 2 5mm AWG12 2 2 5mm AWG12 2 1 5mm 2 0 75mm 2 2 5mm AWG12 2 0 75mm 2 1 5mm 2 1 5mm 2 0 75mm 2 0 75mm 2 1 5mm 2 2 5mm AWG12 2 2 5mm AWG12 2 2 5mm AWG12 2 1 5mm E 2...

Page 30: ...h new filters once every 6 months CLEANING THE HEATEXCHANGER 1 Take off the front panel by removing the screws to make the cleaning easier 2 Clean the indoor unit using a cloth with the water not high...

Page 31: ...ic control board Air filter dirty Back flow of liquid in the refrigerant circulation This occurs when the air in the room becomes very cold for example in the COOLING or DEHUMIDIFYING DRY modes This n...

Page 32: ......

Reviews: