background image

20

Figure 7.5 

P/

N

:1

611

5-

1 B

pressure

400  kPa

•  If the controls are untouched for ~ 30 seconds, the menu will revert back to normal display; 

•  Using the  

 

Menu up button

 and 

 

Menu down button

 scroll through to LEVEL;

•  Use the  

 

Menu up button

 and 

 

Menu down button

 to change the setting to Y;

•  Press the  

 

Enter button

 to save settings and return to the HOME SCREEN;

•  Now restart automatic operation by pressing 

 

Automatic on / manual off button

.

7.2 Using a remote alarm monitoring

ATTENTION: 

Ensure that any and all electrical work is only undertaken by an authorized electrician.

The DynaDrive has available the option to wire in a remote alarm. DynaDrive uses a volt free contact on the 

PCB with 1A maximum, see figure 7.6. The contact is compatible with different types of signal types (optical, 

acoustics, etc). The contact triggers when fault detected & shown on control display.

7.3 Daisy-chain multiple DynaDrive systems

It is possible to run two DynaDrive pumps in parallel, with a shared discharge line. This can be particularly 

useful in applications where the system’s maximum flow rate can be significantly higher than the system’s 

minimum flow rate. For example: if DynaDrive needed a flow rate demand of up to 200L/min at a pressure of 

400kPa. Running two DynaDrive DD90-13 systems in parallel with common discharge would accommodate 

this. One DynaDrive would be designated as the MASTER, with the remaining DynaDrive designated as a 

SLAVE. Each DynaDrive would require its own pressure transducer. When making changes to settings in the 

system, only the MASTER can be adjusted. 
On initial startup, the DynaDrive designated as the MASTER will be the first pump to start. The SLAVE 

DynaDrive will come on if the first pump is unable to maintain set pressure, even when running at 100% 

speed. The next time water is in demand, the SLAVE pump will come on first. This sequence is referred to 

as auto-rotate. To wire up the MASTER and SLAVE pump, refer figure 7.6.

Summary of Contents for DynaDrive DD60-10

Page 1: ...Instructions ATTENTION Please refer to www bit ly dynadrive for any product information updates or simply scan this QR code These can also be found on the product nameplate Please pass these instruct...

Page 2: ...riming and air handling capacity 6 4 4 Power connection 6 4 5 The pressure tank 7 5 FEATURES 8 5 1 System features 8 5 2 DynaDrive display layout 8 5 3 VSD features 9 6 OPERATION 9 6 1 Start up proced...

Page 3: ...ironment The pump enclosure has adequate drainage in the event of leakage Any transport plugs are removed The pipework is correctly sealed and supported The pump is primed correctly The power supply i...

Page 4: ...ar point installations When a pump is installed on a spear or well point a check valve fitted immediately on top of the spear point itself see figure 3 3 Do not install the check valve at the pump or...

Page 5: ...sible to adjust the pressure set point Some plumbing authorities impose a pressure limitation on the pressure of water into a dwelling Consideration of operating pressures should also be given to appl...

Page 6: ...open gate valve to pump When full replace priming plug Ensure outlet nearest to pump is open Ensure all valves in suction line are open Switch on power All LEDs on the display will flash Refer sectio...

Page 7: ...ng to isolate the pressure tank and release the water pressure from the tank beforehand or Release all water pressure from the pressure tank by switching off the pump at the power point and opening th...

Page 8: ...ates reducing the inconvenience of pressure variation in showers etc Allows for independent switch to override DynaDrive operation This could be particularly handy if using a float switch in a source...

Page 9: ...n from onsite brown outs by way of shut down visual alarm auto re try after correct voltage regained Protection from motor locked rotor by way of auto shut down Adaptable for daisy chain multiple pump...

Page 10: ...ve controller measures warm or humid weather It is possible for the DynaDrive controller fan to be running even if the DynaDrive pump isn t Figure 6 2 P N 16115 1 B Pset 400 Pact 0 To start the DynaDr...

Page 11: ...ndby maintaining pressure see figure 6 4 Figure 6 4 P N 16115 1 B Pset 400 Pact 400 6 2 Manual override In addition to automated control DynaDrive can also be run in manual override on should the need...

Page 12: ...and hold the Prime button The pump will turn on and continue to run until the Prime button is released see figure 6 6 While the pump is in manual override the Prime LED will illuminate orange see fig...

Page 13: ...continue to show the pressure set but changes from showing actual pressure to the frequency of power supplying the motor see figure 6 7 This dictates the speed that the motor runs Figure 6 7 P N 16115...

Page 14: ...nstallation chapter The set pressure cannot be changed while the pump is running or in automatic mode To change the set pressure Ensure automated control is turned off To turn the automated control of...

Page 15: ...back to normal display To change the set pressure use the Menu up button or Menu down button Pressure changes are in multiples of 10kPa Once you ve reached your new set point see figure 6 11 Figure 6...

Page 16: ...ust up the min frequency setting refer section 7 4 and install a larger pressure tank If you have any further concerns please contact your local Davey representative 6 6 Decommissioning the DynaDrive...

Page 17: ...override DynaDrive operation DynaDrive has the ability to be overridden by a separate switch This may be of benefit if using a float switch on a source tank eg rainwater tank To wire in an independen...

Page 18: ...ve will pause Davey recommends a float switch cable no longer than 3m when using 2 x 0 25mm2 cable If the switch overrides DynaDrive to pause the DynaDrive display will show a flashing Fault LED The A...

Page 19: ...remote switch Ensure automated control is turned off To turn the automated control off push the Automatic on manual off button The green Automatic LED will turn off see figure 7 4 Figure 7 4 P N 1611...

Page 20: ...hain multiple DynaDrive systems It is possible to run two DynaDrive pumps in parallel with a shared discharge line This can be particularly useful in applications where the system s maximum flow rate...

Page 21: ...uggests limiting the distance between the pumps to 2m To set up multiple DynaDrive to run in a common manifolded system use the following The primary pump is indicated by a solid green Automatic LED e...

Page 22: ...ve controller delegated as the MASTER 7 4 Changing the min frequency The default minimum frequency of DynaDrive is 15Hz This can be changed by Ensure automated control is turned off To turn the automa...

Page 23: ...hrough to Min Freq Use the Menu up button and Menu down button to change the setting to The setting will change by 5Hz Press the Enter button to save settings and return to the HOME SCREEN Now restart...

Page 24: ...the menu will revert back to normal display Using the Menu up button and Menu down button scroll through to Cut in Use the Menu up button and Menu down button to change the setting to adjust the cut i...

Page 25: ...DD60 10 DD90 11 DD90 13 DD160 19 Inlet BSP F 1 1 Discharge outlet BSP M 1 Pressure tank outlet top BSP F 1 Default nominal operating press kPa 400 Number of stages impellers 6 5 6 5 Maximum pump press...

Page 26: ...Frequency incoming power Hz 50 60Hz Input power P1 kW 1 1 1 3 1 6 2 1 Output power P2 kW 0 8 0 9 1 1 1 5 Running current A 7 4 8 6 12 8 Insulation class F IP rating 55 8 5 Materials of construction P...

Page 27: ...not dismantle spring under pressure IMPORTANT Do not use hydrocarbon based or hydrocarbon propelled sprays around the electrical components of this pump During servicing use only approved non petroch...

Page 28: ...n HM60 10T Figure 11 1 16 19 18 14 11 10 9 8 8 8 6 5 7 7 7 12 15 13 20 21 22 23 24 25 4 3 2 1 ITEM NOTES DESCRIPTION QTY REQ D PART NO 1 Casing Front DD60 10 DD90 11 DD90 13 1 13656 6SP 1 Casing Front...

Page 29: ...D60 DD90 series 1 13663 11 Stage body Final DD160 series 1 13675 12 Spacer Destage 60 10 DD90 11 1 13696 1 13 B Washer Cup Not applicable to DD160 models As required 13666 13 Washer Cup DD160 2 13693...

Page 30: ...30 NOTES...

Page 31: ...31...

Page 32: ...he right to replace defective parts of the product with parts or components of similar quality grade and composition where an identical part or component is not available Goods presented for repair ma...

Reviews: