4. Refrigerant charging procedure
In addition to conventional charging procedures, the following requirements shall be followed;
Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses
or lines should be as short as possible to minimise the amount of refrigerant contained in them.
Cylinders should be kept upright.
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
Label the system when changing is complete (if not already).
Extreme care should be taken to not overfill the refrigeration system.
Prior to recharging the system, it should be pressure tested with the appropriate purging gas. The system
shall be leak tested on completion of changing but prior to commissioning. A follow up leak test should be
carried out prior to leaving the site.
Protection and Failure Codes
No.
Display
Protection Code Description
1
E3
No water protection
2
E5
Power supply exceeds operation range
3
E6
Excessive temp difference between inlet and outlet water
(Insufficient water flow protection)
4
Eb
Ambient temperature too high or too low protection
5
Ed
Anti-freezing reminder
No.
Display
Failure Code Description
1
E1
High pressure protection
2
E2
Low pressure protection
3
E4
3 phase sequence protection (three phase only)
4
E7
Water outlet temp too high or too low protection
5
E8
High exhaust temp protection
6
EA
Evaporator overheat protection (only at cooling mode)
7
P0
Controller communication failure
8
P1
Water inlet temp sensor failure
9
P2
Water outlet temp sensor failure
10
P3
Gas exhaust temp sensor failure
11
P4
Evaporator coil pipe temp sensor failure
12
P5
Gas return temp sensor failure
13
P6
Cooling coil pipe temp sensor failure
14
P7
Ambient temp sensor failure
15
P8
Cooling plate sensor failure
16
P9
Current sensor failure
17
PA
Restart memory failure
18
F1
Compressor drive module failure
19
F2
PFC module failure
20
F3
Compressor start failure
21
F4
Compressor running failure
22
F5
Inverter board over current protection
23
F6
Inverter board overheat protection
24
F7
Current protection
25
F8
Cooling plate overheat protection
26
F9
Fan motor failure
27
Fb
Power filter plate No-power protection
28
FA
PFC module over current protection