DAT 6000
12
PRELIMINARY
How to Program the module
The input type is in-field configurable by means of the dip-switches. The input
type configuration is made by SW1..SW3 dip-switches which can be used to
set up to 8 different input types. The standard correspondance between the dip-
switch setting and the relative input type is shown in the tables below. It can be
modified using the ‘PRO6000’ software and the PRODAT-03 interface.
By this way, it is possible to reconfigure the module for a wide range of input
signal types at any time.
Also the CLK signal’s digital filter can be set to 1 ms or 10 ms (half-period
duration) by a dip-switch (SW4). The digital filter eliminates all the signal
variations shorter than the specified time, avoiding undesired command
simulations.
Hereafter the standard tables of the various modules are shown:
DAT6012 and DAT6013 modules, having a limited number of possible input
types, are availables with a fixed table. Whereas DAT6011 and DAT6021 are
available as in Tab.A or in Tab.B, indicating the choice at the order, or in any
desired configuration using the software, as previously mentioned. DAT6023
module is not configurable; consequently the input type (V or mA) must be
defined at the order phase.
SW1
SW2
SW3
Input Input
Tab.A Tab.B
0
0
0
Tc J
50 mV
0
0
1
Tc K
100 mV
0
1
0
Tc T
500 mV
0
1
1
Tc E
1000 mV
1
0
0
Tc R
---
1
0
1
Tc S
---
1
1
0
Tc B
---
1
1
1
Tc N
---
SW1
SW2
SW3
Input
0
0
0
Res. L
0
0
1
Res. H
0
1
0
Pt100
0
1
1
Ni100
1
0
0
Pt1000
1
0
1
Ni1000
1
1
0
Pot. L
1
1
1
Pot. H
DAT6011 - DAT 6021
DAT6012
DAT6013
SW1
SW2
SW3
Input
x
x
0
10 V
x
x
1
20 mA