Setting the operating
mode
Sequence of operations
•
: (
Outsi
de) The output gets switched on, when
the displayed physical value isn’t between the low limit
value (L.LI) and the high limit value (H.LI).
•
(
Warm
) The output gets switched on, when the
displayed physical value is lower than the low limit value
(L.LI), When the displayed current value is higher or equal
than L.LI, than the state of output doesn’t change.
The output gets switched off when the displayed current
value is higher than the upper limit value (H.LI). When the
displayed current value is lower or equal than H.LI, than the
state of limit output doesn’t change.
This operating mode is used in other DATCON instruments.
Here you can use it at any control task where the AC
current is the process value and you can control the
process through the limit outputs.
•
(
Cool
) The output gets switched on, when the
displayed physical value is higher than the high limit value
(H.LI). When the displayed current value is lower or equal
than H.LI, than the state of limit output doesn’t change.
The output gets switched off when the displayed current
value is lower than the lower limit value (L.LI). When the
displayed current value is lower or equal than L.LI, than the
state of limit output doesn’t change.
This operating mode is used in other DATCON instruments.
Here you can use it at any control task where the
temperature is the process value and you can control the
process through the limit outputs.
•
: (
On
= switched on) The output is switched on
independently from the measured value.
Exit from the operating
mode menu item
6. After selecting the limit output mode press
MENU button
you will see:
.
7. If you had selected the
or the
mode, there is no
need to do any further settings. For finishing the operation,
please go on from the point
Exit from the menu item
.
Summary of Contents for DT4120 PS Series
Page 1: ...DT4120 xx xx PS Temperature Resistance Potentiometer Meter Transmitter Operating Instructions...
Page 84: ...DT4120 xx xx PS 84 20170324 V0 10 2 Application example Analog output option...
Page 85: ...DT4120 xx xx PS 20170324 V0 85 RS232 communication interface option...
Page 86: ...DT4120 xx xx PS 86 20170324 V0 RS485 communication interface option...
Page 87: ...DT4120 xx xx PS 20170324 V0 87 RS485 bus topology...
Page 90: ...DT4120 xx xx PS 90 20170324 V0...
Page 91: ...DT4120 xx xx PS 20170324 V0 91...
Page 92: ......