BWS-T4 Series
Instructions manual
Serie BWS-T4
Manuale istruzioni
16
16
Application with two muting sensors, passage permitted only for package 1:
A
S
B
d1 = D
Muting sensor connection:
contact of A
contact of B
24 V
DC
BWS-T4N
terminals
9
MUTE A
8
MUTE B
11
MUTE C
10
MUTE D
N.C.
N.C.
D:
minimum distance sdo that the
muting
sensors keep
active the request; it depends on the parcel length: D <
L.
d
1
:
necessary maximum distance so that the muting
request is accepted; it depends on the parcel speed:
d
max
[cm]= v[m/s] * 3[s] * 100
This distance must not allow to activate both sensors
and the
muting
with the accidental passage of a
person.
Application with four muting sensors and only photocell S1:
Power cable
Light cable
Muting cable
RX cable
TX cable
Muting
signalizer
Start & Test
button
Protect the
cables
BWS-T4
control-unit
Applicazione con due sensori di muting e caso di passaggio permesso solo al pacco 1:
A
S
B
d1 = D
Collegamento dei sensori di muting:
contatto di A
contatto di B
24 V
DC
morsettiera
BWS-T4N
9
MUTE A
8
MUTE B
11
MUTE C
10
MUTE D
N.C.
N.C.
D:
distanza minima affinché i sensori di
muting
mantengano attiva la richiesta; è funzione della
lunghezza del pacco: D < L.
d
1
:
distanza massima necessaria affinché la richiesta di
muting venga accettata; è funzione della velocità del
pacco:
d
max
[cm]= v[m/s] * 3[s] * 100
Applicazione con quattro sensori di muting e solo la fotocellula S1:
Power cable
Light cable
Muting cable
RX cable
TX cable
Muting
signalizer
Start & Test
button
Protect the
cables
BWS-T4
control-unit