WARNING: ELECTRICITY CAN KILL
ALWAYS disconnect the power BEFORE connecting
the unit.The fuse rating should be 6 Amps.
1) ALWAYS remove the plug connectors when inserting wires with a
screwdriver.
2) An appropriate and readily accessible set of disconnection devices
(e.g. automatic fuses) MUST be provided as part of the installation.
3)
The building mains supply MUST incorporate appropriate short-
circuit backup protection (e.g. a fuse or circuit breaker) of High
Breaking Capacity (HBC, at least 1500A).
4)
Use cables of adequate current carrying capacity (at least
0.75mm
2
) and temperature range.
WARNING: THE UNIT IS NOT FUSED.
Use external fuses for Mains phases: L1,L2,L3,
Generator phase: L1,L2,L3, Battery positive: BAT(+).
Install the fuses as nearly as possible to the unit in a
place easily accessible for the user.
The fuse rating should be 6 Amps.