DKG-153 

MANUAL START UNIT 

INSTALLATION AND OPERATING INSTRUCTIONS

 

 

 

 

 

The model DKG-153 is a microprocessor controlled 
unit  used  to  start  and  stop  the  genset  manually 
using  the  key  switch  and  pushbuttons  on  the  front 
panel.  

When the engine is running, the unit monitors fault 
conditions and shuts-down the engine automatically 
in  the  occurrence  of  an  alarm.  The  alarms  are 
identified  by  a  group  of  LEDs  displaying  only  the 
first occurring one. 

The unit has jumper selectable options for 50/60Hz 
nominal frequency and the auxiliary output function. 
The  selection  is  made  by  the  position  of  a  single 
jumper situated at the left side panel of the unit. 

If the jumper is placed between: 
A & B :

 50Hz nominal, AUX is Preheat output 

B & C :

 60Hz nominal, AUX is Preheat output 

C & D :

 60Hz nominal, AUX is Stop output 

D & A :

 50Hz nominal, AUX is Stop output. 

In the 

OFF

 position, the DC supply is removed from 

the  module,  thus  zero  power  consumption  is 
achieved. 

 

 

The  unit  powers  up  when  the 

RUN

  position  on  the 

front 

panel 

is 

selected. 

If 

required, 

the 

PREHEAT/STOP  (

button  may  be  depressed 

as  long  as  needed.  This  will  activate  the 

AUXILIARY

 relay output and the related front panel 

led marked (

). 

The engine is started using the pushbutton marked 

CRANK (I)

. This will also energize the fuel solenoid 

output.  Once  the  engine  is  running,  the  switch 
should  be  released.  However  the  internal  logic 
inhibits cranking when the engine fires up. 

The  alarm  checking  is  only  enabled  after  the 

protection  hold-off  timer

  is  expired.  This  timer 

resets to 12 seconds if: 
    -the unit is powered up, 
    -or 

CRANK (I) 

button is pressed, 

    -or 

PREHEAT/STOP (

button is pressed, 

    -or the engine gets running. 

The  occurrence  of  below  fault  signals  (which  are 
close  on  fault)  will  cause  the  engine  to be stopped 
immediately: 

       -Overspeed, 
       -Underspeed, 
       -High engine temperature, 
       -Low oil pressure, 
       -Auxiliary shutdown. 

If  a  fault  condition  occurs,  the 

FUEL

  solenoid  will 

be deenergized. If the auxiliary output is set to 

Stop

 

option,  it  will  be  energized  during  stop timeout and 
the  led  associated  with  this  condition  will  turn  on. 
To  reset  the  fault  condition,  turn  the  switch  to  the 

OFF

 position for a few seconds. 

The 

Charge  Fail 

condition  is  treated  as  a  warning 

only and do not cause the engine to stop. The input 
monitors the 

D+

 terminal of the charge alternator. 

To shut-down the engine manually: 

-if  the 

AUX

  output  is  set  to 

Stop

  option,  press  the 

PREHEAT/STOP  (

)

  button  until  the  engine 

comes to rest. Then select the 

OFF

 position on the 

switch. 
-else select the 

OFF

 position on the switch. 

OPERATION

 

DESCRIPTION

 