Term Function
Technical data
Description
14
BATTERY POSITIVE
+12 or 24VDC
The positive terminal of the DC Supply shall
be connected to this terminal. The unit
operates on both 12V and 24V battery
systems.
15
J1939
+
Digital communication
port
Connect the J1939 port of an electronic
engine to these terminals.
The 120 ohm terminating resistors are inside
the unit. Please do not connect external
resistors.
Use a twisted cable pair or coaxial cable for
best results.
16
J1939
-
17
GROUND
O VDC
Power supply negative connection.
18
Current
transformer
inputs, 5A-AC
Connect the generator current transformer
terminals to these inputs. Do not connect the
same current transformer to other instruments
otherwise a unit fault will occur. Connect each
terminal of the transformer to the unit‟s related
terminal. Do not use common terminals. Do
not use grounding. Correct polarity of
connection is vital. If the measured power is
negative, then change the polarity of the
current transformer. The secondary winding
rating shall be 5 Amperes. (For ex. 200/5
Amps).
19
CURR_1-
20
FUEL LEVEL SENDER
Input, 0-5000 ohms
Analogue fuel level sender connection. Do not
connect the sender to other devices. The input
has
programmable
resistor
value
and
connects to various senders.
21
COOLANT TEMP. SENDER
Input, 0-5000 ohms
Analogue
high
temperature
sender
connection. Do not connect the sender to
other devices. The input has programmable
characteristics and connects to any kind of
sender.
22
OIL PRESSURE SENDER
Input, 0-5000 ohms
Analogue oil pressure sender connection. Do
not connect the sender to other devices. The
input has programmable characteristics and
connects to any kind of sender.
23
CHARGE
Input and output
Connect the charge alternator‟s D+ terminal to
this terminal. This terminal will supply the
excitation current and measure the voltage of
the charge alternator.
24
FUEL RELAY
Output 1A/28VDC
This relay is used for fuel solenoid control.
25
START RELAY
Output 1A/28VDC
This relay controls the engine cranking.
26
RELAY-1 (ALARM RELAY)
Output 1A/28VDC
This relay has programmable function,
selectable from a list.
27
RELAY-2 (STOP RELAY)
Output 1A/28VDC
This relay has programmable function,
selectable from a list.