DK-40 USER MANUAL V2.6 (02.08.2011)
K13D01-E - 27 -
No
Description
Adjustment Range
Factory set
P40
RL5 function selection
0
: Alarm
1
: Fan
2
: Load
3
: No load
4
: Motor run
5
: Motor stopped
Refer chapter 8 for more details.
2
P41
Fan On Temperature (RL5)
30 ... (P09-2)
Refer chapter 8 for more details.
85 °C
P42
Delta T Fan Off
Temperature (RL5)
5 ... 15
Refer chapter 8 for more details.
10 °C
P43
Reserved
-
0
P44
Reserved
-
0
P45
Pressure loss preventing
method
0:
standard operation
1:
step increase/decrease
2:
dynamic calculation
0
P46
Reserved
-
0
P47
Reserved
-
0
P48
Connection topology
1:
1 phase
2:
2 phases
3:
3 phases
3
P49
Phase L1 calibration
1 ...32767
1186
P50
Phase L2 calibration
1 ... 32767
1186
P51
Phase L3 calibration
1 ... 32767
1186
P52
Low Frequency Alarm
Enable
0
: Disable
1
: Enable
If this parameter is set to
0
, the
P53 parameter will not be
displayed.
1
P53
Low Frequency Alarm Limit
10.0 ... 60.0 Hz
48.0 Hz
P54
High Frequency Alarm
Enable
0
: Disable
1
: Enable
If this parameter is set to
0
, the
P55 parameter will not be
displayed.
1