![Dataforth MAQ20-RTD31 Hardware User Manual Download Page 38](http://html1.mh-extra.com/html/dataforth/maq20-rtd31/maq20-rtd31_hardware-user-manual_3652553038.webp)
MA1044 MAQ20-RTD31/-RTD41 Hardware User Manual
Page 34 of 38
Address Range 100 - 699 : Module Configuration
Start
Address
Read/
Write
Number of
Registers
Contents
Description
Data Range
Data
type
100
R/W
5
Input Sensor & Range
for each channel
See Table 7
Default = 0
0, 1, 2, 4
INT16
119
W
1
Save to EEPROM
0 = Sensor/Range, Average
Weight, Scan List
0
INT16
120
R/W
5
Average Weight
Weight for AVG Calculation,
Default = 3
0 to 15
INT16
140
R/W
5
Channel Enable
0 = Disable 1 = Enable,
Default = 1
0 or 1
INT16
Address Range 700 - 999 : Alarm Configuration
Start
Address
Read/
Write
Number of
Registers
Contents
Description
Data Range
Data
type
700
R/W
1
Alarm Status,
Low-Low
To clear a Latched alarm
write a 0 to the
corresponding channel bit.
0 to 65,535
INT16
701
R/W
1
Alarm Status,
Low
To clear a Latched alarm
write a 0 to the
corresponding channel bit.
0 to 65,535
INT16
702
R/W
1
Alarm Status,
High
To clear a Latched alarm
write a 0 to the
corresponding channel bit.
0 to 65,535
INT16
703
R/W
1
Alarm Status,
High-High
To clear a Latched alarm
write a 0 to the
corresponding channel bit.
0 to 65,535
INT16
704
R/W
1
Alarm Enable
1 = Enabled 0 = Disabled
INT16
709
W
1
Save Alarm Parmeters
to EEPROM
Writing 1 saves the Alarm
Configuration, High Limit,
Low Limit, High-Low
Deadband, High-High
Limit, Low-Low Limit and
HHLL Deadband to local
non-volatile memory.
1
INT16
710
R/W
5
Alarm Configuration
Alarm Configuration
INT16
730
R/W
5
High Limit
High Alarm Limit
Table 17
INT16
750
R/W
5
Low Limit
Low Alarm Limit
Table 17
INT16
770
R/W
5
High Low Deadband
Deadband for High Low
Alarm
Table 17
INT16
790
R/W
5
High-High Limit
High-High Alarm Limit
Table 17
INT16
810
R/W
5
Low-Low Limit
Low-Low Alarm Limit
Table 17
INT16
830
R/W
5
High-High Low-Low
Deadband
Deadband for High-High
Low-Low Alarm
Table 17
INT16