![Dataforth MAQ20-RTD31 Hardware User Manual Download Page 34](http://html1.mh-extra.com/html/dataforth/maq20-rtd31/maq20-rtd31_hardware-user-manual_3652553034.webp)
MA1044 MAQ20-RTD31/-RTD41 Hardware User Manual
Page 30 of 38
Address Range 1000 - 1699 : Module Data
Start
Address
Read/
Write
Number of
Registers
Contents
Description
Data Range
Data
type
1000
R/W
6
Channel Data
Data for each of 6
Channels
Tables 14, 5
INT16
1016
R/W
1
Alarm Status
Status of Low-Low Alarm
0 to 65,535
INT16
1017
R/W
1
Alarm Status
Status of Low Alarm
0 to 65,535
INT16
1018
R/W
1
Alarm Status
Status of High Alarm
0 to 65,535
INT16
1019
R/W
1
Alarm Status
Status of High-High Alarm
0 to 65,535
INT16
1030
R/W
6
Data Minimum
Minimum value for each of
6 Channels
Table 14
INT16
Address Range 1000 - 1699 : Module Data
Start
Address
Read/
Write
Number of
Registers
Contents
Description
Data Range
Data
type
1050
R/W
6
Data Maximum
Maximum value for each
of 6 Channels
Table 14
INT16
1070
R/W
6
Data Average
Average for each of 6
Channels
Table 14
INT16
1090
R/W
8
Channel 0 Data
Last 8 readings for Ch 0
Tables 14, 15
INT16
1100
R/W
8
Channel 1 Data
Last 8 readings for Ch 1
Tables 14, 15
INT16
1110
R/W
8
Channel 2 Data
Last 8 readings for Ch 2
Tables 14, 15
INT16
1120
R/W
8
Channel 3 Data
Last 8 readings for Ch 3
Tables 14, 15
INT16
1130
R/W
8
Channel 4 Data
Last 8 readings for Ch 4
Tables 14, 15
INT16
1140
R/W
8
Channel 5 Data
Last 8 readings for Ch 5
Tables 14, 15
INT16
Address Range 1700 - 1899 : Input Ranges
Start
Address
Read/
Write
Number of
Registers
Contents
Description
Data Range
Data
type
1700
R
1
Range Count
Number of ranges supported
5
INT16
1710
R
1
Range 0
Engineering -fs.
-32,767 to 32,768
INT16
1711
R
1
Range 0
Future Use
-32,767 to 32,768
INT16
1712
R
1
Range 0
Enginfs
-32,767 to 32,768
INT16
1713
R
1
Range 0
Future Use
-32,767 to 32,768
INT16
1714
R
1
Range 0
+fs & -fs multiplier Factor 10^X
-32,767 to 32,768
INT16
1715
R
1
Range 0
Engineering Units ("C", "V", etc)
A to Z
ASCII
1716
R
1
Range 0
Engineering Units ("C", "V", etc)
A to Z
ASCII
1717
R
1
Range 0
Future Use
-32,767 to 32,768
INT16
1718
R
1
Range 0
Count Value of -fs.
-32,767 to 32,768
INT16
1719
R
1
Range 0
Future Use
-32,767 to 32,768
INT16
1720
R
1
Range 0
Count Value of +fs.
-32,767 to 32,768
INT16