background image

9

2.2.1 3-Way Chilled Water Valves

Unit Model

Valve Size

Valve CV

DACx 07

1”

10.0

DACx 09

1”

10.0

DACx 11

1-1/4”

10.0

DACx 13

1-1/2”

19.0

DACx 15

1-1/2”

19.0

DACx 18

2”

46.0

DACx 22

2”

46.0

DACx 26

2”

46.0

DACx 30

2”

46.0

DACx 40

2”

46.0

DACx 45

2”

46.0

DACx 50

2”

46.0

2.2.2 2-Way Chilled Water Valves

Close-off

Unit Model

Valve Size

Valve CV

Pressure, psi

DACx 07

1”

10.0

200

DACx 09

1”

10.0

200

DACx 11

1 1/4”

10.0

200

DAC x 13

1 1/2”

19.0

200

DACx 15

1 1/2”

19.0

200

DACx 18

2”

46.0

200

DACx 22

2”

46.0

200

DACx 26

2”

46.0

200

DACx 30

2”

46.0

200

DACx 40

2”

46.0

200

DACx 45

2”

46.0

200

DACx 50

2”

46.0

200

2.3

Condensate Drain Piping

Every indoor unit has a 3/4" copper stub provided for condensate removal.  A union is

recommended at the field connection which will permit easy disconnection from the unit for cleaning.

A trap should be built into the drain line to prevent air from backing up into the unit.  Drain

lines should be pitched downward not less than 1/4" for each ten feet of horizontal run.  Do not
reduce the size of the drain line.

Some applications have no convenient means of allowing a gravity drain.  In this case, a

condensate pump can be used.  These come either factory mounted or shipped loose.  Factory
mounted condensate pumps do not require a separate power source.

Condensate pumps shipped loose (or field provided) typically require a dedicated 110 volt power

source.  Field pipe connections must be made to the pump discharge connection.  A check valve
must be installed to prevent short cycling.  See also condensate pump electrical requirements in
Section 3.9.

Summary of Contents for DAC Series

Page 1: ...DATAAIRE SERIES Operation and Maintenance Manual Chilled Water 7 50 ton INSTALLATION OPERATION MAINTENANCE...

Page 2: ...ce to Data Aire units should be done by qualified individuals with an adequate background in areas such as HVAC electrical plumbing and electronics as applicable Service performed by unauthorized or u...

Page 3: ...s 9 2 3 Condensate Drain Piping 9 2 4 Humidifier Piping 10 2 4 1 Steam Generator Humidifier 10 2 4 2 Dry Steam Humidifier 10 2 5 Leak Testing 10 3 0 ELECTRICAL CONNECTIONS 11 3 1 Electrical Service 11...

Page 4: ...nts cont d 5 4 Humidifier Canisters 14 5 5 Fuses 14 5 6 Heating Elements 15 6 0 WARRANTY 16 7 0 CONTACT DATA AIRE 17 MONTHLY MAINTENANCE INSPECTION CHECKLIST 19 QUARTERLY MAINTENANCE INSPECTION CHECKL...

Page 5: ...ipping damage can occur and a visual inspection of the outer crating immediately upon delivery should be performed Note any external damage or other transportation damage on the freight carrier s form...

Page 6: ...Installation of units above equipment that could sustain water damage should be avoided 1 4 1 Downflow Units Downflow units will typically sit on an elevated flooring system known as a raised floor T...

Page 7: ...t comes ready for immediate installation In some instances in may be necessary to store the equipment for a period of time If you must store the equipment it should be done in a dry area out of the we...

Page 8: ...decorative doors as this could prevent the door from swinging open Standard chilled water units have a 3 way chilled water valve An option for a 2 way valve is also available In either case the water...

Page 9: ...sate removal A union is recommended at the field connection which will permit easy disconnection from the unit for cleaning A trap should be built into the drain line to prevent air from backing up in...

Page 10: ...idifier has a drain at the bottom which is factory piped to the main condensate drain line The dispersion tube also has a drain line No additional field piping is required 2 4 2 Dry Steam Humidifier T...

Page 11: ...tions in the unit control panel to ensure they are tight Screw terminals may become loose in transit Tightening of wiring connections is the responsibility of the installing contractor 3 5 Remote Shut...

Page 12: ...a High Condensate Water Level alarm The wiring for this must be done in the field on pumps that ship loose Factory mounted pumps come pre wired 3 9 Condensate Probe A condensate probe for sensing unde...

Page 13: ...e a thorough unit installation Start up is not complete until the DAP III control panel settings are established 4 2 Wiring Diagrams Every Data Aire unit comes with a wiring diagram These diagrams are...

Page 14: ...urn the adjustment screw on the end of the motor mounting channel until the proper belt tension is attained Retighten the four mounting bolts Damage can also occur to belts that are overtightened The...

Page 15: ...requiring fast acting fuses 5 6 Heating Elements Heating elements do not normally require maintenance However sometimes they may accumulate a film of dust or dirt when unused for extended periods of t...

Page 16: ...uipment goods or merchandise arising out of any defect in or failure of any equipment of its manufacture and Buyer hereby waives any claim against Seller arising out of such claim This warranty shall...

Page 17: ...s E mail service dataaire com Service tech_support dataaire com Technical Support engineering dataaire com Engineering sales dataaire com Sales Web site www dataaire com Job information Model Number D...

Page 18: ...18...

Page 19: ...ment Runtimes Blower _________ hrs Reheat No 1 _________ hrs Reheat No 2 _________ hrs Reheat No 3 _________ hrs Humidifier _________ hrs Dehumidification _________ hrs Chilled Water Cooling _________...

Page 20: ...20...

Page 21: ...ation of temperature sensor 7 1 ___ Check calibration of humidity sensor 7 2 ___ Check calibration of discharge air sensor 7 3 ___ Check calibration of chilled water temperature sensor 7 4 DAP III gro...

Page 22: ...Air Filters 14 B Bearings 14 Belts 14 C Cable Water Sensing 12 Condensate Cable 12 Condensate Probe 12 Condensate Pumps 12 Contact Data Aire 17 Controls 13 DAP II Control Panel 13 Wiring Diagrams 13...

Page 23: ..._____________________________________________________________ _____________________________________________________________________________________ ____________________________________________________...

Page 24: ...3 www dataaire com e mail sales dataaire com A Member of the CS Group of Companies 2009 Data Aire Inc Data Aire Inc reserves the right to make design changes for the purpose of product improvement or...

Reviews: