3.0 ELECTRICAL CONNECTIONS

Before proceeding with the electrical connections, make certain that the volts, hertz, and phase
correspond to that specified on the unit electrical nameplate.  Use copper conductors only.

3.1

Electrical Service

Check to be sure the service provided by the utility is sufficient to handle the additional load imposed

by this equipment.

3.2

Nameplate Ratings

Refer to the unit electrical nameplate for equipment electrical requirements.  Minimum circuit ampacity,

(MCA) also known as wire sizing amps, will dictate the minimum required wire gauge.  Maximum
overcurrent protection (MOP) device amps will dictate the maximum circuit breaker or fuse size.

3.3

Grounding

The unit cabinet must have an uninterrupted true earth ground.  An electrical ground wire of adequate

size must be connected to the ground lug provided inside the main electrical box.

3.4

Voltage Tolerance

The supply voltage to the unit must be within 10% of the voltage indicated on the unit electrical

nameplate.  Phase to phase imbalance must not exceed 3%.  The local utility company should be
contacted for correction of improper line voltage.  Deviation from voltage ratings can cause premature
failures and possibly void unit warranties.

Check the wiring connections in the unit control panel to ensure they are tight.  Screw

terminals may become loose in transit.  Tightening of wiring connections is the responsibility

of the installing contractor.

3.5

Remote Shutdown

Every Data Aire chilled water unit has remote shutdown contacts.  These are intended for a field

supplied dry contact or switch to be wired across two terminals.  When the contact or switch opens, the
control circuit power is interrupted and the unit shuts down, including the control panel.  The control
circuit is 24 VAC and the field provided contact or switch should have a minimum rating of 10 amps.

The remote shutdown contacts are always terminals #1 and #2 on the terminal block designated

TB1.  The unit will ship with a factory wired metal jumper clip that connects terminal #1 to terminal #2.
Remove this clip prior to installing the field wires.

3.6

Remote Alarm Contacts

The 

DAP III

, microprocessor control panel provides a remote alarm output contact that can be field

accessed on terminals #11 and #13 of terminal block TB1.  This is a Normally Open, Close on Alarm,
dry contact, intended to be used in a control circuit not exceeding 5 amps at 24 VAC.

This programmable output contact will close on a failure and remain closed until the alarm is no

longer present.  Three additional alarm output contacts come with the optional relay module.  The terminal
designations for these alarm output contact pairs are #40 and #42; #43 and #45; and #48 and #50.

Summary of Contents for DAC Series

Page 1: ...DATAAIRE SERIES Operation and Maintenance Manual Chilled Water 7 50 ton INSTALLATION OPERATION MAINTENANCE...

Page 2: ...ce to Data Aire units should be done by qualified individuals with an adequate background in areas such as HVAC electrical plumbing and electronics as applicable Service performed by unauthorized or u...

Page 3: ...s 9 2 3 Condensate Drain Piping 9 2 4 Humidifier Piping 10 2 4 1 Steam Generator Humidifier 10 2 4 2 Dry Steam Humidifier 10 2 5 Leak Testing 10 3 0 ELECTRICAL CONNECTIONS 11 3 1 Electrical Service 11...

Page 4: ...nts cont d 5 4 Humidifier Canisters 14 5 5 Fuses 14 5 6 Heating Elements 15 6 0 WARRANTY 16 7 0 CONTACT DATA AIRE 17 MONTHLY MAINTENANCE INSPECTION CHECKLIST 19 QUARTERLY MAINTENANCE INSPECTION CHECKL...

Page 5: ...ipping damage can occur and a visual inspection of the outer crating immediately upon delivery should be performed Note any external damage or other transportation damage on the freight carrier s form...

Page 6: ...Installation of units above equipment that could sustain water damage should be avoided 1 4 1 Downflow Units Downflow units will typically sit on an elevated flooring system known as a raised floor T...

Page 7: ...t comes ready for immediate installation In some instances in may be necessary to store the equipment for a period of time If you must store the equipment it should be done in a dry area out of the we...

Page 8: ...decorative doors as this could prevent the door from swinging open Standard chilled water units have a 3 way chilled water valve An option for a 2 way valve is also available In either case the water...

Page 9: ...sate removal A union is recommended at the field connection which will permit easy disconnection from the unit for cleaning A trap should be built into the drain line to prevent air from backing up in...

Page 10: ...idifier has a drain at the bottom which is factory piped to the main condensate drain line The dispersion tube also has a drain line No additional field piping is required 2 4 2 Dry Steam Humidifier T...

Page 11: ...tions in the unit control panel to ensure they are tight Screw terminals may become loose in transit Tightening of wiring connections is the responsibility of the installing contractor 3 5 Remote Shut...

Page 12: ...a High Condensate Water Level alarm The wiring for this must be done in the field on pumps that ship loose Factory mounted pumps come pre wired 3 9 Condensate Probe A condensate probe for sensing unde...

Page 13: ...e a thorough unit installation Start up is not complete until the DAP III control panel settings are established 4 2 Wiring Diagrams Every Data Aire unit comes with a wiring diagram These diagrams are...

Page 14: ...urn the adjustment screw on the end of the motor mounting channel until the proper belt tension is attained Retighten the four mounting bolts Damage can also occur to belts that are overtightened The...

Page 15: ...requiring fast acting fuses 5 6 Heating Elements Heating elements do not normally require maintenance However sometimes they may accumulate a film of dust or dirt when unused for extended periods of t...

Page 16: ...uipment goods or merchandise arising out of any defect in or failure of any equipment of its manufacture and Buyer hereby waives any claim against Seller arising out of such claim This warranty shall...

Page 17: ...s E mail service dataaire com Service tech_support dataaire com Technical Support engineering dataaire com Engineering sales dataaire com Sales Web site www dataaire com Job information Model Number D...

Page 18: ...18...

Page 19: ...ment Runtimes Blower _________ hrs Reheat No 1 _________ hrs Reheat No 2 _________ hrs Reheat No 3 _________ hrs Humidifier _________ hrs Dehumidification _________ hrs Chilled Water Cooling _________...

Page 20: ...20...

Page 21: ...ation of temperature sensor 7 1 ___ Check calibration of humidity sensor 7 2 ___ Check calibration of discharge air sensor 7 3 ___ Check calibration of chilled water temperature sensor 7 4 DAP III gro...

Page 22: ...Air Filters 14 B Bearings 14 Belts 14 C Cable Water Sensing 12 Condensate Cable 12 Condensate Probe 12 Condensate Pumps 12 Contact Data Aire 17 Controls 13 DAP II Control Panel 13 Wiring Diagrams 13...

Page 23: ..._____________________________________________________________ _____________________________________________________________________________________ ____________________________________________________...

Page 24: ...3 www dataaire com e mail sales dataaire com A Member of the CS Group of Companies 2009 Data Aire Inc Data Aire Inc reserves the right to make design changes for the purpose of product improvement or...

Reviews: